Input variable
Parameter
- Version A

distance between lower edge of the flange and

product surface

- version B, C and D

distance between lower edge of the transducer

and product surface

Dead zone

0.8 m (2.6 ft)

Measuring range
- Liquids

up to 45 m (147.6 ft)

- Solid

up to 25 m (82 ft)

Accuracy (similar to DIN EN 60770-1)
Reference conditions acc. to DIN EN 61298-1
- Temperature

18 … +30°C (64 … +86°F)

- Relative humidity

45 … 75 %

- Atmospheric pressure

860 … 1060 mbar (86 … 106 kPa/

12.5 … 15.4 psi)

Characteristic curve deviation and measurement characteristics

4)

Average temperature coefficient of the

zero signal (temperature error elec-

tronics)

0.06 %/10 K

Resolution, general

max. 1 mm

Ultrasonic frequency

18 kHz

Interval

>2 s (dependent on the parameter adjustment)

Beam angle at -3 dB

Adjustment time

5)

>3 s (dependent on the parameter adjustment)

Accuracy

better than 0.2 % or ±6 mm (see diagram)

4)

Relating to the nominal range, incl. hysteresis and repeatability, determined

acc. to the limit point method.

5)

Time to output the correct level (with max. 10 % deviation) after a sudden

level change.

42

OPTISOUND 3050 C - 4 ... 20 mA/HART - four-wire