beautypg.com

KROHNE OPTISOUND 3050C 4wire EN User Manual

Page 32

background image

vessel wall (with solids). To adapt the sensor to these different

conditions, you should first select in this menu item "Liquid" or

"Solid".

Medium

Liquid

With solids, you can also choose between "Powder/Dust",

"Granular/Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted

perfectly to the product and measurement reliability, partic-

ularly in products with bad reflective properties, is considerably

increased.
Enter the requested parameter via the appropriate keys, save

your settings and jump to the next menu item with the [–>] key.

Apart from the medium, the shape of the vessel can also

influence the measurement. To adapt the sensor to these

conditions, this menu item offers (depending on either liquid or

solid is detected) different options. For Liquid these are

Storage tank, Stilling tube, Open vessel or Stirred vessel, for

Solid Silo or Bunker.

Vessel shape

Storage tank

Enter the requested parameter via the appropriate keys, save

your settings and jump to the next menu item with the [–>] key.

To suppress fluctuation in the measured value display, e.g.

caused by a turbulent product surface, an integration time can

be set. This time can be between 0 and 999 seconds. Please

note that the reaction time of the entire measurement will be

longer and the sensor will react to quick changes of the

measured value with a corresponding delay. In general, a time

of a few seconds is sufficient to smooth the measured value

display.

Damping

0 s

Vessel shape

Damping

32

OPTISOUND 3050 C - 4 ... 20 mA/HART - four-wire

Setup with the indicating/adjustment module

30518

-EN
-050914