Addendum to Operating and Instruction Manual for “Modis” Converters

KROHNE Ltd

Rutherford Drive

Park Farm Industrial Estate

Wellingborough

Northamptonshire

NN8 6AE

UK

Tel. +44 1933 408 500

Fax +44 1933 408 501

WWW.KROHNE.com

Page 18 of 18

Ex

Non-Ex

Control input (IS)

Not available

Function

All operating data programmable galvanically
isolated from supply, CPU and other outputs.

Operation

Passive, loop-powered

External supply
voltage

7 – 30V DC

Current

4.5 mA

Control signals

7-30V DC for HIGH
0-2V or open terminals for LOW
Connect ONLY to certified IS circuits with the
maximum values:
Ui = 30V, Ii = 250mA, Pi = 1W

PROFIBUS PA

Hardware

See table above

See table above

Software

See table above

See table above

Fieldbus
Foundation (IS)

Pending

Pending

Hardware

Designed to ISA and IEC 1158-2 physical
layer. Standards applicable to type 121
device profile.
Connection: polarity independent
Connect ONLY to certified IS circuits
according to the FISCO model with the
maximum values:
Ui = 30V, Ii = 250mA, Pi = 1W

Designed to ISA and IEC 1158-2 physical
layer. Standards applicable to type 121
device profile.
Connection: polarity independent
Bus data: 9V – 32V; 11mA typical

Ambient
Temperature

-20 to 65°C

-20 to 65°C