Addendum to Operating and Instruction Manual for “Modis” Converters

KROHNE Ltd

Rutherford Drive

Park Farm Industrial Estate

Wellingborough

Northamptonshire

NN8 6AE

UK

Tel. +44 1933 408 500

Fax +44 1933 408 501

WWW.KROHNE.com

Page 13 of 18

0

1

0 0 0 0

= non-specific

0

1

0 0 0 1

= last usable value

0

1

0 0 1 0

= substitute-set

0

1

0 0 1 1

= initial value

0

1

0 1 0 0

= sensor conversion not accurate

0

1

0 1 0 1

= engineering unit violation (unit not in the
valid set)

0

1

0 1 1 0

= sub-normal

0

1

0

1

1

1

= configuration error

0

1

1

0

0

0

= simulated value

0

1

1

0

0

1

= sensor calibration

Status = good (Non-Cascade)

1

0

0 0 0 0

= ok

1

0

0 0 0 1

= update event

1

0

0 0 1 0

= active advisory alarm (priority < 8)

1

0

0 0 1 1

= active critical alarm (priority > 8)

1

0

0 1

0 0

= unacknowledged update event

1

0

0 1

0 1

= unacknowledged advisory alarm

1

0

0 1

1 0

= unacknowledged critical alarm

1

0

1

0

0

0

= initiate fail safe

1

0

1

0

0

1

= maintenance required

Status = Limits

0 0 = ok
0 1 = low limited
1 0 = high limited
1 1 = constant

Please test the first two (Quality) to check the quality of the measuring value:

Good (non Cascade)

measuring value is ok and can be used

Uncertain

the measuring value can be used, although the accuracy is not
confirmed (e. g. measuring value is frozen or A/D-value is outside
of the valid range)

Bad

the measuring value is not acceptable and cannot be used for
further processing.

Good (Cascade)

will not be supported, because it is not applicable for the device

Diagnosis

If the internal diagnostic detects a error, additional information will be transmitted in the
Master. The meaning of this information are described in the GSD-file under
UNIT_DIAG_BIT(i).