Addendum to Operating and Instruction Manual for “Modis” Converters
KROHNE Ltd
•
Rutherford Drive
•
Park Farm Industrial Estate
•
Wellingborough
•
Northamptonshire
•
NN8 6AE
•
UK
Tel. +44 1933 408 500
•
Fax +44 1933 408 501
•
WWW.KROHNE.com
Page 15 of 18
D
I
1
Power
Supply
Power
Supply
Fieldbus
Current
Output
Fieldbus
Current
Output
D
I
1
D
D
I I
Non-Ex-Version
Ex-Version
4-20mA
U=8-30V
+
-
Shield
PROFIBUS-
PA
4-20mA
U=8-30V
-
+
Shield
PROFIBUS-
PA
4. Menu Settings for PROFIBUS-PA
The following settings need to be made for Operation of the MFC 081/ 85 i on a PROFIBUS-
PA network. Note, that the address can be set over the communication service “Set slave
address” from the master.
Function (Fct.)
Description
3.8.4
LOCATION
Tag name setting (measuring point no.) max. 10 characters
Characters assignable to each place:
A-Z 0-9 or "_" (blank character)
3.11.0
Text, measuring-point tag (max. 10 characters)
Characters assignable to each place:
A-Z 0-9 or "_" (blank character)
3.11.1
PROTOCOL
•
PROFI PA
3.11.2
ADDRESS
Set address
Range: 00-126 for PROFIBUS-PA (default 126)
3.11.3
BAUD RATE
BLOCKED