1 Important information for installation: PLEASE NOTE
•
Location and position as required,
but electrode axis X – • – • – • – X
must be approximately horizontal in a
horizontal pipe run.
Y terminal box or converter housing
•
Measuring tube must be completetly filled at all times.
•
Direction of flow is arbitrary. Arrow on flowmeter can normally be ignored.
For exceptions, refer to Section ”Factory settings” in the installation and operating
instructions for the signal converter.
•
Stud bolts and nuts: to fit, make sure there is sufficient room next to the pipe flanges.
•
Vibration: support the pipeline on both sides of the compact flowmeter.
Level of vibration in conformity with IEC 068-2-34: 20-500 Hz, random / 2g runs / 30 minutes /
x, y, z directions.
•
Do not expose to direct sunlight,
fit a sunshade if necessary, not included with flowmeter, to be provided by customer.
X
X
•
Handling
Do not lift flowmeter by the
signal converter housing or
the terminal box.
Do not set flowmeter down on signal
converter housing or terminal box.
•
Use only solventless detergents to clean the signal converter housing (polycarbonate).
•
Temperatures
For operating pressure and vacuum load based on connection standards, see Section 6
“Limits“.
Ambient temperature
Product temperature
Compact systems
-25 to +60 °C (-13 to +140 °F)
-20 to +
0
60 °C (-4 to +140 °F)
-25 to +40 °C (-13 to +104 °F)
-20 to +140 °C (-4 to +284 °F)
- EEx version
-25 to +40 °C (-13 to +104 °F)
-20 to +140 °C (-4 to +284 °F)
IFS 6000 F
-25 to +60 °C (-13 to +140 °F)
-20 to +
0
60 °C (-4 to +140 °F)
- flange connections
-25 to +40 °C (-13 to +104 °F)
-20 to +180 °C (-4 to +356 °F)
- other connections
-25 to +40 °C (-13 to +104 °F)
-20 to +140 °C (-4 to +284 °F)
- EEx version
-25 to +40 °C (-13 to +104 °F)
-20 to +140 °C (-4 to +284 °F)