beautypg.com

Description of hart interface, 2 software history – KROHNE SMARTSENS PH 8530 EN User Manual

Page 33

background image

DESCRIPTION OF HART INTERFACE

7

33

SMARTSENS PH 8530

www.krohne.com

11/2013 - 4002544802 - MA SMARTSENS PH 8530 R02 en

Description of HART interface

7.1 General description

The open HART

®

protocol, which can be used for free, is integrated into the sensor for

communication.

Devices which support the HART

®

protocol are classified as either operating devices or field

devices. When it comes to operating devices (Master), both manual control units (Secondary
Master) and PC-supported workstations (Primary Master) are used in, for example, a control
centre.

HART

®

field devices include measuring sensors, signal converters and actuators. The field

devices range from 2-wire to intrinsically safe versions for use in hazardous areas.

The HART

®

data are superimposed over the analogue 4...20 mA signal via FSK modem. This way,

all of the connected devices can communicate digitally with one another via the HART

®

protocol

while simultaneously transmitting the analogue signals.

When it comes to the field devices and secondary masters, the FSK or HART

®

modem is

integrated. If a PC is used, an external modem must be connected to the serial interface
(USB interface). There are, however, other connection variants which can be seen in the
following connection figures.

7.2 Software history

HART

®

identification codes and revision numbers

INFORMATION!
In the table below, "x" is a placeholder for possible multi-digit alphanumeric combinations,
depending on the available version.

Release date

SW version

HW version

HART

®

Device Revision

DD Revision

2013-04-01

1.0.x

1.0.x

1

1

Manufacturer ID:

69 (0x45)

Device:

195 (0xC3)

Device Revision:

1

DD Revision:

1

HART

®

Universal Revision:

7

FC 475 system SW.Rev.:

≥ 3.7

PDM version:

≥ 8.0

FDT version:

≥ 1.2

.book Page 33 Monday, November 18, 2013 4:32 PM