DEVICE DESCRIPTION

14

OPTIBAR 5060

www.krohne.com

04/2014 - 4003591801 - AD OPTIBAR 5060 Ex ia R01 en

OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T with integrated electronics Z (4…20 mA),
H (4…20 mA/HART) or A (4…20 mA/HART with SIL qualification), version with double chamber
housing D, W or R with housing version/protection category P (with M12 x 1)

Circuit for the display and adjustment

module: (spring contacts in the "Ex-i"

terminal compartment)

in protection type intrinsic safety Ex ia IIC

Only for connection to the display and adjustment module.

In the double chamber housing version, the display and

adjustment module in the terminal compartment should only

be equipped if there is no OPTIBAR * 5060 with electronics S, T

connected.

Circuit between sensor and external

electronics

in protection type intrinsic safety Ex ia IIC

For the OPTIBAR * 5060 VGK5/6/D*A/W C in the version with

the cable permanently mounted to the sensor and external

electronics, the length of the supplied cable between the

external housing and the sensor should not exceed 180 m and

for the OPTIBAR * 5060 VGK5/6/D*A/W C with external

housing it should not exceed 50 m.

OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T with integrated electronics S or T, only single
chamber housing version)

Supply and signal circuit: (terminals

5,6,7,8 in the electronics compartment)

in protection type intrinsic safety Ex ia IIC

For connection to the intrinsically safe circuit of an OPTIBAR *

5060 VGK5/6/D**C with integrated electronics H, A, P, F for

differential pressure measurement.

The rules for interconnecting intrinsically safe circuits

between OPTIBAR * 5060 with electronics S or T and the

OPTIBAR * 5060 VGK5/6/D**C are observed when the overall

inductance and overall capacity of the connecting cable

between OPTIBAR * 5060 VGK5/6/D**C and OPTIBAR * 5060

with electronics S or T

L

cable

= 330 μH and C

cable

= 2.00 μF are not exceeded.

Take into account the following cable inductances L

i

and cable

capacities C

i

when using the supplied connection cable

between OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T and

OPTIBAR * 5060 with electronics S or T.

L

i

= 0.62 μH/m

C

i wire/wire

= 150 pF/m

C

i wire/shield

= 270 pF/m

OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T version with separate cable outlet

Circuit between sensor unit and

external electronics (terminal 1 - yellow,

terminal 2 - white, terminal 3 - red,

terminal 4 - black)

in protection type intrinsic safety Ex ia IIC

For the OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T in the

version with the cable permanently mounted to the sensor

unit and external electronics, the length of the supplied cable

between the external housing and the sensor unit should not

exceed 180 m.