DEVICE DESCRIPTION

2

13

OPTIBAR 5060

www.krohne.com

04/2014 - 4003591801 - AD OPTIBAR 5060 Ex ia R01 en

OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T with integrated electronics Z (4…20 mA),
H (4…20 mA/HART

®

) or A (4…20 mA/HART

®

with SIL qualification)

Indicating and adjustment circuits:
(terminals 5, 6, 7, 8)

1)2)3)

in protection type intrinsic safety Ex ia IIC

For connection of an OPTIBAR * 5060 with integrated

electronics S or T for differential pressure measurement.

The rules for interconnecting intrinsically safe circuits

between OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T and

OPTIBAR * 5060 with electronics S or T are observed when the

overall inductance and overall capacity of the connecting

cable between

OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T and

OPTIBAR * 5060 with electronics S or T

L

cable

= 330 μH and C

cable

= 1.98 μF are not exceeded.

Take into account the following cable inductances L

i

and cable

capacities C

i

when using the supplied connection cable

between OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T and

OPTIBAR * 5060 with electronics S or T.

L

i

= 0.62 μH/m

C

i wire/wire

= 150 pF/m

C

i wire/shield

= 270 pF/m

Intrinsically safe circuit for the display and adjustment module
OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T with integrated electronics Z (4…20 mA),
H (4…20 mA/HART) or A (4…20 mA/HART with SIL qualification), version with single chamber
housing A, K, V or 8

Circuit for the display and adjustment

module: (spring contacts in the "Ex-i"

electronics compartment)

in protection type intrinsic safety Ex ia IIC

Only for connection to the display and adjustment module.

OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T with integrated electronics Z (4…20 mA),
H (4…20 mA/HART) or A (4…20 mA/HART with SIL qualification), version with double chamber
housing D, W or R

Circuit for the display and adjustment

module: (spring contacts in the "Ex-i"

terminal compartment)

in protection type intrinsic safety Ex ia IIC

Only for connection to the display and adjustment module.

1)

In the "Ex-i" electronics compartment for OPTIBAR in version with single chamber housing A, K V or 8.

2)

In the "Ex-i" terminal compartment for OPTIBAR in version with double chamber housing D, W or R.

3)

Additional connector for OPTIBAR in version with double chamber housing D, W, R and housing

version/protection category P (with M12 x 1).

and circuit for the display and

adjustment module: (spring contacts in

the "Ex-i" electronics compartment)

in protection type intrinsic safety Ex ia IIC

Only for connection to the display and adjustment module.

In the double chamber housing version, the display and

adjustment module in the terminal compartment should only

be equipped if there is no OPTIBAR P* 5060 with electronics S,

T connected.