DEVICE DESCRIPTION
2
13
OPTIBAR 5060
www.krohne.com
04/2014 - 4003591801 - AD OPTIBAR 5060 Ex ia R01 en
OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T with integrated electronics Z (4…20 mA),
H (4…20 mA/HART
®
) or A (4…20 mA/HART
®
with SIL qualification)
Indicating and adjustment circuits:
(terminals 5, 6, 7, 8)
1)2)3)
in protection type intrinsic safety Ex ia IIC
For connection of an OPTIBAR * 5060 with integrated
electronics S or T for differential pressure measurement.
The rules for interconnecting intrinsically safe circuits
between OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T and
OPTIBAR * 5060 with electronics S or T are observed when the
overall inductance and overall capacity of the connecting
cable between
OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T and
OPTIBAR * 5060 with electronics S or T
L
cable
= 330 μH and C
cable
= 1.98 μF are not exceeded.
Take into account the following cable inductances L
i
and cable
capacities C
i
when using the supplied connection cable
between OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T and
OPTIBAR * 5060 with electronics S or T.
•
L
i
= 0.62 μH/m
•
C
i wire/wire
= 150 pF/m
•
C
i wire/shield
= 270 pF/m
Intrinsically safe circuit for the display and adjustment module
OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T with integrated electronics Z (4…20 mA),
H (4…20 mA/HART) or A (4…20 mA/HART with SIL qualification), version with single chamber
housing A, K, V or 8
Circuit for the display and adjustment
module: (spring contacts in the "Ex-i"
electronics compartment)
in protection type intrinsic safety Ex ia IIC
Only for connection to the display and adjustment module.
OPTIBAR * 5060 VGK5/6/D*A/W C/U/0/H/T with integrated electronics Z (4…20 mA),
H (4…20 mA/HART) or A (4…20 mA/HART with SIL qualification), version with double chamber
housing D, W or R
Circuit for the display and adjustment
module: (spring contacts in the "Ex-i"
terminal compartment)
in protection type intrinsic safety Ex ia IIC
Only for connection to the display and adjustment module.
1)
In the "Ex-i" electronics compartment for OPTIBAR in version with single chamber housing A, K V or 8.
2)
In the "Ex-i" terminal compartment for OPTIBAR in version with double chamber housing D, W or R.
3)
Additional connector for OPTIBAR in version with double chamber housing D, W, R and housing
version/protection category P (with M12 x 1).
and circuit for the display and
adjustment module: (spring contacts in
the "Ex-i" electronics compartment)
in protection type intrinsic safety Ex ia IIC
Only for connection to the display and adjustment module.
In the double chamber housing version, the display and
adjustment module in the terminal compartment should only
be equipped if there is no OPTIBAR P* 5060 with electronics S,
T connected.