beautypg.com

Technical data – KROHNE BM 26 BASIC_ADVANCED Quickstart EN User Manual

Page 26

background image

4

TECHNICAL DATA

26

BM 26 BASIC/ADVANCED

www.krohne.com

10/2012 - 4000346904 - QS BM 26 Basic-Adv R04 en

Electrical connections

Power supply

Power supply

Power supply

Power supply

Voltage

Non-Ex:

Non-Ex:

Non-Ex:

Non-Ex:

9...32 VDC

Ex ia:

Ex ia:

Ex ia:

Ex ia:

Refer to supplementary instructions or approval certificates

Cable entry

M20 × 1.5

Intrinsically-safe circuit data for

Ex ia-approved devices

Refer to supplementary instructions or approval certificates

PROFIBUS PA

PROFIBUS PA

PROFIBUS PA

PROFIBUS PA

Description

-

PROFIBUS PA protocol Profile

A&B, ver.3.0 (EN 50170 vol.2)

FOUNDATION Fieldbus

FOUNDATION Fieldbus

FOUNDATION Fieldbus

FOUNDATION Fieldbus

Description

FOUNDATION Fieldbus protocol

-

Approvals and certification

CE

This device fufills the statutory requirements of the EC directives.

The manufacturer certifies successful testing of the product by

applying the CE mark.

Explosion protection

Explosion protection

Explosion protection

Explosion protection

ATEX

II 1 G Ex ia IIC T4...T6

2

II 1 G Ex ia IIC T4...T6

2

II 2 G Ex ib IIC T4...T6

3

II 2 G Ex ib IIC T4...T6

3

Other standards and approvals

Other standards and approvals

Other standards and approvals

Other standards and approvals

EMC

Electromagnetic Compatibility Directive 2004/108/EC in conjunction

with EN 61326-1 (2006)

Vibration resistance

Vibration class 4M4 according to EN 60721-3-4

1 The customer must specify the position of the converter at the top or the bottom of the analog transmitter
2 Conventional or FISCO systems intrinsically-safe systems
3 FISCO systems intrinsically-safe systems

Module output

FOUNDATION™ Fieldbus

PROFIBUS PA

Order code

xF45xDxxxxx (PR)