INSTALLATION

2

7

OPTIWAVE 5200 C/F

www.krohne.com

08/2013 - 4001905202 - QS OPTIWAVE 5200 R02 en

2.7 Installation

2.7.1 Pressure and temperature ranges

For more data on pressure ratings, refer to the "Technical Data" chapter in the handbook.

DANGER!
If the ambient temperature is more than +70

°

C / +158

°

F, there is a risk of injury if you touch the

device. Use a protective cover or metallic grid to prevent injury.

Figure 2-5: Pressure and temperature ranges

1 Flange temperature

Non-Ex devices: Depends on the type of antenna, process connection and the seal material. Refer to the table that fol-
lows.
Ex devices: see supplementary operating instructions

2 Ambient temperature for operation of the display

-20...+60°C / -4...+140°F
If the ambient temperature is not between these limits, the display screen switches off automatically. The device con-
tinues to operate.

3 Ambient temperature

Non-Ex devices: -40...+80°C / -40...+176°F
Ex devices: see supplementary operating instructions

4 Process pressure

Depends on the type of antenna and process connection. Refer to the table that follows.

Antenna type

Process

connection

Seal

Process connection

temperature

Process pressure

[°C]

[°F]

[barg]

[psig]

PP

Wave Horn

G 1½;

1½ NPT

-

-20...+100

-4...+212

-1...16

-14.5...232

PTFE

Wave Horn

Flange with

PTFE plate

-

-50...+150

-58...+302

-1...40

-14.5...580

Metallic Horn

Wave Guide

Flange

Metaglas® with

FKM/FPM

-40...+200

1

-40...+392

1

-1...40

2

-14.5...580

2

Metaglas® with

Kalrez® 6375

-20...+250

1

-4...+482

1

-1...40

2

-14.5...580

2

Metaglas® with

PFA

-60...+130

1

-76...+266

1

-1...40

2

-14.5...580

2

Metaglas® with

EPDM

-50...+130

1

-58...+266

1

-1...40

2

-14.5...580

2

1 Higher temperature on request
2 Higher pressure on request