2.7 Installation
2.7.1 Pressure and temperature ranges
For more data on pressure ratings, refer to the "Technical Data" chapter in the handbook.
DANGER!
If the ambient temperature is more than +70
°
C / +158
°
F, there is a risk of injury if you touch the
device. Use a protective cover or metallic grid to prevent injury.
Figure 2-5: Pressure and temperature ranges
1 Flange temperature
Non-Ex devices: Depends on the type of antenna, process connection and the seal material. Refer to the table that fol-
lows.
Ex devices: see supplementary operating instructions
2 Ambient temperature for operation of the display
-20...+60°C / -4...+140°F
If the ambient temperature is not between these limits, the display screen switches off automatically. The device con-
tinues to operate.
3 Ambient temperature
Non-Ex devices: -40...+80°C / -40...+176°F
Ex devices: see supplementary operating instructions
4 Process pressure
Depends on the type of antenna and process connection. Refer to the table that follows.
Antenna type
Process
connection
Seal
Process connection
temperature
Process pressure
[°C]
[°F]
[barg]
[psig]
PP
Wave Horn
G 1½;
1½ NPT
-
-20...+100
-4...+212
-1...16
-14.5...232
PTFE
Wave Horn
Flange with
PTFE plate
-
-50...+150
-58...+302
-1...40
-14.5...580
Metallic Horn
Wave Guide
Flange
Metaglas® with
FKM/FPM
-40...+200
1
-40...+392
1
-1...40
2
-14.5...580
2
Metaglas® with
Kalrez® 6375
-20...+250
1
-4...+482
1
-1...40
2
-14.5...580
2
Metaglas® with
PFA
-60...+130
1
-76...+266
1
-1...40
2
-14.5...580
2
Metaglas® with
EPDM
-50...+130
1
-58...+266
1
-1...40
2
-14.5...580
2
1 Higher temperature on request
2 Higher pressure on request