Operation – KROHNE OPTIWAVE 5200 C_F Quickstart EN User Manual
Page 36
4
OPERATION
36
OPTIWAVE 5200 C/F
www.krohne.com
08/2013 - 4001905202 - QS OPTIWAVE 5200 R02 en
•
[
] or [
] for the selection of the current
output range (4-20 mA/3.6E, 4-20, 3.8-
20.5/3.6E, etc.).
•
[^
^
^
^] to confirm.
•
[>>>>] to change Scale 4 mA.
•
[>>>>] to change the position of the cursor.
•
[
] to decrease the value or [
] to
increase the value.
•
[^
^
^
^] to confirm.
Use this step to give the 4 mA output
setting (0% limit) in the tank. Refer to the
illustrations that follow. Illustration 1
shows the settings for level. Illustration 2
shows the settings for distance.
•
[>>>>] to change Scale 20 mA.
•
[>>>>] to change the position of the cursor.
•
[
] to decrease the value or [
] to
increase the value.
•
[^
^
^
^] to confirm.
Use this step to give the 20 mA output
setting (100% limit) in the tank. Refer to
the illustrations that follow. Illustration 1
shows the settings for level. Illustration 2
shows the settings for distance.
•
[
] or [
] for the selection of the error
delay (0 s, 10 s, 20 s, 30 s, 1 mn, 2 mn,
5 mn or 15 mn).
•
[^
^
^
^] to confirm.
The time after which the current output
changes to an error value. The error value
shows that there is a measurement error.
•
[>>>>] to change the tag name.
•
[>>>>] to change the position of the cursor.
•
[
] to decrease the alphanumeric value
(A, B, ..., 1, 2, ...) or [
] to increase the
alphanumeric value.
•
[^
^
^
^] to confirm.
The device has an identification code (tag
name). The supervisor can enter a
maximum of 8 numbers or letters.
•
2 × [^
^
^
^] to confirm.
•
[
] or [
] for the selection of the save
option (STORE NO or STORE YES).
•
[^
^
^
^] to confirm.
Set to STORE YES to save and use the data.
Set to STORE NO to cancel the changes to
the device settings.
Screen
Steps
Description