• Up and Down Keys:
These keys are used to move upwards and downwards in

screens to reach a desired item and to change setpoints

and user settings. They have an auto increment/decrement

feature for some of the configurations and values. When

you first press one of the keys and value changes by 1

count, then wait 1/2 second and changes slowly until the

key is released or if held for 3 or more seconds it will

change the value quickly.

• Help Key:
Pressing the Help key from any screen displays helpful

information about that screen. From the menu screen,

general help information is displayed as to how to use the user

interface. To return to the previous screen press the Help or

Select keys, or press Menu key to go to the menu screen. If a

small down arrow appears in the lower right hand corner then

there is off screen content below what is displayed. Press the

down arrow to scroll down to this information. After scrolling

down an up arrow will appear in the upper right hand corner

to indicate off screen content above what is displayed.

UIM LED’s
The three LED’s to the right of the LCD indicate the status

of the overall system. The red LED indicates that a fault

has been detected and the system has stopped running.

It is on continuously for soft faults and flashes for hard

faults. The Yellow LED indicates that the boiler is in a

ready mode waiting for a call for heat command. When

on continuously the Green LED indicates that the system

is in the heating mode. If it is flashing it indicates that the

UIM is in the initialization mode and the touch switches are

being calibrated.
The VF

®

boiler has a display on the UIM which is a scaled display

indicating the current firing rate of the boiler (25% to 100%).

Fault Messages and Troubleshooting Guide
The EMC 5000 modulation system does excessive self-

diagnostics and displays detected faults on the UIM display

in an easy to read manner. There are approximately 80

different faults that can be detected. Some of the faults are

caused by internal problems and some by external causes.

The faults create different types of system lockouts (shut

down). Hard lockouts are serious problems that require the

user to manually restart the system. Soft lockouts can be reset

by the user or after 60 minutes the system will automatically

clear the error and restart. Auto Reset lockouts will monitor

the cause of the fault and it the fault clears itself the system

resets itself. The following table shows the fault messages

and some possible troubleshooting hints: