FIGURE 12B. DIRECT VENT, VERTICAL VENT TERMINATION WITH HORIzONTAL INTAKE.

FIGURE 12C. DIRECT VENT USING TWT WITH VERTICAL INTAKE.

Option B (Figures 12B & 12C)

assures no recirculation of flue gases.

70 EQUIVALENT FEET (27.4m)

OF VENTING (MAX.) AL 29-4C

®

HORIzONTAL AIR INTAKE

PVC PIPE 70

EQUIVALENT FEET (27.4m)

AIR INTAKE TERMINAL

NOTES:

• IF THE EXHAUST VENT TERMINAL IS WITHIN 10’ (3.0m)

OF A WALL OR A PARAPET, IT MIUST EXTEND A MINIMUM

OF 2’ (0.6m) ABOVE THE WALL OR PARAPET.

• ON SIDEWALL VENT INSTALLATION, REFER

TO FIGURE 9F FOR SPACING SPECIFICATIONS

• FOR EXHAUST AND AIR INTAKE PIPE INSTALLATIONS

(CLEARANCES, SUPPORT, ETC.) REFER TO FIGURES

12 AND 12A.

VERTICAL AIR INTAKE MUST BE

12” (305mm) ABOVE ANTICIPATED

SNOW LEVEL.

PVC PIPE 70 EQUIVALENT FEET (27.4m)

70 EQUIVALENT FEET (27.4m)

OF VENTING (MAX.) AL 29-4C

®

NOTES:

• IF THE EXHAUST VENT TERMINAL IS WITHIN 10’ (3.0m)

OF A WALL OR A PARAPET, IT MIUST EXTEND A MINIMUM

OF 2’ (0.6m) ABOVE THE WALL OR PARAPET.

• ON SIDEWALL VENT INSTALLATION, REFER

TO FIGURE 9G FOR SPACING SPECIFICATIONS

• FOR EXHAUST AND AIR INTAKE PIPE INSTALLATIONS

(CLEARANCES, SUPPORT, ETC.) REFER TO FIGURES

12 AND 12A.