ELECTRICAL CONNECTIONS
4
19
OPTISONIC 3400
www.krohne.com
10/2013 - 7313222100 - AD CSA OPTISONIC 3400 -en- R01
The exact I/O-configuration for circuits A, B, C and D is order-specific and can be determined by
the CG35 number shown on the I/O sticker inside the terminal compartment. Therefore check
the data on the back of the UFC 400 electronics unit. The CG35 number contains 10 characters
of which the last three characters (XYZ) determine the configuration of the I/O circuits:
For schematic overviews of the CG35 numbers, refer to
Non-I.S. I/O connections
on page 21 and
refer to
I.S. I/O connections
on page 23. These overviews do not show all details. The exact
connection diagram of a specific UFC 400 signal converter can be found on the sticker inside the
terminal compartment.
Figure 4-2: Electrical connections
1 Unscrew interlocking head screw
2 Turn cover counterclockwise and remove
3 Open / close safety lid of mains supply section
4 Mains supply & signal / data terminals
Terminals
Terminals
Terminals
Terminals
Function, electrical data
Function, electrical data
Function, electrical data
Function, electrical data
L, N
L+, L-
Connections for mains supply, always non- I.S.
100...230 V AC, +10%/-15%, 22 VA
12...24 V DC, +30%/-25%, 12 W
24 V AC, +10%/-15%, 22 VA
24 V DC, +30%/-25%, 12 W
U
m
= 253 V
A, A-, A+
B, B-
C, C-
D, D-
Connections for signal I/Os (PELV circuits), non-I.S. or I.S., are dependent on the
specific version of the UFC 400 converter ordered. Consult the tables with CG35
numbers for details.
CG35
CG35
CG35
CG35
****
****
****
X
XX
X
YYYY
Z
ZZ
Z
Pos 1...4
5
6
7
8
9
10
determine I/O circuits
INFORMATION!
For more detailed information regarding I/O connections for USA / Canada (FM / CSA) DIV1
systems, see the KROHNE Altometer control drawing nr; 8.30736.31 A