CONNECTION OF SEPARATE SYSTEMS

3

15

OPTISONIC 3400

www.krohne.com

10/2013 - 7313222100 - AD CSA OPTISONIC 3400 -en- R01

3.1 General

In the case of separate systems, the electrical connection between OPTISONIC 3000 F/...-DIV1
ultrasonic flow sensor and UFC 400 F...-DIV1 ultrasonic signal converter is established via a
signal cable of type MR06-RG316. This cable consists of six coaxial cables surrounded by an
additional screen and outer insulation layer. The ends of the coaxial cables are provided with
SMB plugs. The signal cable is included with the field system by KROHNE.

3.2 Cable marking

The SMB plugs of the coaxial cables are marked by yellow tubing with a black number of
subsequently 1.1, 1.2, 2.1, 2.2, 3.1 and 3.2. The first number represents the path 1, 2 or 3 and the
second the transducer of that path (1 or 2). The marking of the SMB counter-plugs in the
connection box of the signal converter is respectively 1.1, 1.2, 2.1, 2.2, 3.1 and 3.2. Also refer to

Signal cable connections (field versions)

on page 16 for the connection of the several connection

box types.

3.3 Cable parameters

The maximum permitted total capacitance and inductance for the connecting cable is:

C

L

= C

a

(C

o

) -C

i

= 528 - 11.6 = 516.4 nF

L

L

= L

a

(L

o

) - L

i

= 800 - 500 = 300 μH

The cable supplied by the manufacturer has the following parameters:
distributed capacitance C

C

(core/screen) = 94 pF/m

distributed inductance L

C

(core/screen) = 0.24 μH/m

INFORMATION!
The standard length of the signal cable is 5 m / 16.4 ft. In case a longer length is required, please
contact your local representative for detailed information.

INFORMATION!
More than 30 m signal cable length is not recommendable, it will have a negative effect on the
measuring accuracy.