SAFETY-RELATED CHARACTERISTICS

7

13

H250 M40

www.krohne.com

02/2012 - 4000904201 MA H250 M40 SIL R01 en

H250/M40/HT/K*-SK

H250/M40/HT/K*-SK

H250/M40/HT/K*-SK

H250/M40/HT/K*-SK with 1 or 2 fail-safe limit switches

fail-safe limit switches

fail-safe limit switches

fail-safe limit switches (MIN/MAX) 1 and welded

welded

welded

welded

process connections

H250/M40/HT/K*-SK

H250/M40/HT/K*-SK

H250/M40/HT/K*-SK

H250/M40/HT/K*-SK with 1 or 2 standard limit switches

standard limit switches

standard limit switches

standard limit switches (MIN/MAX) 6 and welded

welded

welded

welded

process connections

λ

SD

λ

SU

λ

DD

λ

DU

SFF 2 DC

D

MTBF

SIL AC 3

Stress profile 2
(low stress)

0 FIT

177 FIT

10 FIT

58 FIT

76%

14%

432 years

SIL2

Stress profile 4
(high stress)

0 FIT

219 FIT

10 FIT

114 FIT

66%

8%

308 years

SIL2

T[Proof] 4

1 year

2 years

5 years

PFD

AVG

5

2.77*E-04

5.29*E-04

1.28*E-03

λ

SD

λ

SU

λ

DD

λ

DU

SFF 2 DC

D

MTBF

SIL AC 3

Stress profile 2
(low stress)

0 FIT

208 FIT

10 FIT

97 FIT

69%

9%

342 years

SIL2

Stress profile 4
(high stress)

0 FIT

250 FIT

10 FIT

152 FIT

63%

6%

260 years

SIL2

T[Proof] 4

1 year

2 years

5 years

PFD

AVG

5

4.63*E-04

8.84*E-04

2.15*E-03

1 The switching contact output is connected to a fail-safe NAMUR amplifier (e.g.

Pepperl+Fuchs KF**-SH-Ex1). The failure rates of the amplifier are not included in the
listed failure rates.

2 The number listed is for reference only. The SFF must be determined for the complete

subsystem.

3 SIL AC (architectural constraints) means that the calculated values are within the range

for hardware architectural contraints for the corresponding SIL level.

4 It is assumed that proof testing is performed with a proof test coverage of 99%.
5 The PFD

AVG

was calculated for profile 2 using the Markov modelling. The results must be

considered in combination with PFD

AVG

values of other devices of the Safety Instrumented

Function (SIF) in order to determine suitability for a specific Safety Integrity Level (SIL)
For SIL1 applications, the PFD

AVG

value needs to be < 10

-1

.

For SIL2 applications, the PFD

AVG

value needs to be < 10

-2

.

6 The switching contact output is connected to a standard NAMUR switching amplifier (e.g.

Pepperl+Fuchs KF**-SR2-Ex*.W). The failure rates of the amplifier are not included in the
listed failure rates.

MA_H250_M40_SIL2_R01_en_904201_PRT.book Page 13 Thursday, March 1, 2012 10:08 AM