Modbus protocol, 8 holding registers, 1 counter parameters – KROHNE IFC 050 Converter Modbus EN User Manual
Page 13

MODBUS PROTOCOL
6
13
IFC 050
www.krohne.com
09/2012 - 4002202601 - AD Modbus IFC 050 R01 en
6.8 Holding registers
All holding registers in the Modbus protocol address range from 40000 to 49998 are mapped into
the range 0 to 9998. This is done to give systems with restriction on the address range access to
the device.
Some parameters of the device can be accessed as Modbus "holding registers".
Function code 03 (0x03) for "Read" operations and function code 16 (0x10) for "Write" operations.
The holding registers are grouped into the following different sections.
6.8.1 Counter parameters
Modbus protocol
address
Description and settings
Converter Fct.
No.
Type
Number of
registers
1st
2nd
40000
0
counter 1 function
counter 1 function
counter 1 function
counter 1 function
1 = sum counter
2 = + counter
3 = - counter
0 = off
C3.1.1
byte
1
40001
1
counter 2 function
counter 2 function
counter 2 function
counter 2 function
1 = sum counter
2 = + counter
3 = - counter
0 = off
C3.2.1
byte
1
41000
1000
set counter Cnt1 or read Cnt1
set counter Cnt1 or read Cnt1
set counter Cnt1 or read Cnt1
set counter Cnt1 or read Cnt1 [m
3
] or [kg]
C3.1.4
float
2
41002
1002
set counter Cnt2 or read Cnt2
set counter Cnt2 or read Cnt2
set counter Cnt2 or read Cnt2
set counter Cnt2 or read Cnt2 [m
3
] or [kg]
C3.2.4
float
2
41004
1004
preset counter 1
preset counter 1
preset counter 1
preset counter 1 [m
3
] or [kg]
C3.1.2
float
2
41006
1006
preset counter 2
preset counter 2
preset counter 2
preset counter 2 [m
3
] or [kg]
C3.2.2
float
2