Stabilization, Recovery characteristics, Start-up time – KEPCO HSF-PFC 50W Series Operator Manual User Manual
Page 5: Holdup time, Dielectric strength, Insulation resistance, Leakage current, Safety, Vibration, Shock

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: [email protected]
083013
228-1532 REV 13
5
III — SPECIFICATIONS (STANDARD) - CONTINUED
STABILIZATION:
Source Effect (full load): 0.2% typ.; 0.3% max.
Range: 90-132V a-c or 170-265V a-c,
Load Effect (10% to 100% Load Change):
0.5% typ.; 1.5% max.
Temperature Effect: 0.5% typ.; 1.0% max.
Range: -10° to 71°C
Combined Effect: 0.9% typ.; 1.8% max. (includes
source, load, and temperature effects).
Time Effect (1/2 hr-8 hr at 25°C):
0.2% typ.; 0.5% max.
RECOVERY CHARACTERISTICS: A step load
change from 50% to 100% produces less than +4% output
excursion. Recovery occurs to within +1% of the original
setting in <1 ms (load change t
r
or t
f
equal to or greater
than 50
µsec).
START-UP TIME:
500 ms. max, 300 ms typ. (100V a-c)
200 ms. max, 100 ms typ. (240V a-c)
HOLDUP TIME:
30 ms. typ., 20 ms. min.
DIELECTRIC STRENGTH:
Between input and output:
2KV a-c for one minute
Between input and case (ground):
2KV a-c for one minute.
Between output and case (ground):
500V a-c for one minute, cutout current 20 mA
INSULATION RESISTANCE: Between input and
ground, output and ground, input and output:
100 Megohms min. (500V d-c).
LEAKAGE CURRENT
0.24 mA maximum (IEC 950 and UL 1950, 120V a-c)
0.48 mA maximum (IEC 950 and UL 1950, 240V a-c).
SAFETY: Units are designed to meet UL60950 3rd [1st]
Edition, CSA 22.2 No. 60950 and EN 60950 and are CE
marked per the Low Voltage Directive (LVD), 73/23/EEC
and 93/68/EEC. The standards do not apply with DC input
operation.
EMI: Designed to meet FCC Class B (100-120V a-c) and
VDE 0871 Class B (220-240V a-c).
VIBRATION: (non-operating, one hour on each one of
the three axes):
5-10 Hz, 10 mm amplitude.
10-55 Hz, 2g acceleration.
SHOCK: (non-operating, one-half sinusoidal pulse, three
shocks to each axis):
Acceleration: 60g
Duration: 11ms +5ms
OPERATING TEMPERATURE: See Figure 4.
FIGURE 4. % OUTPUT POWER RATING VS.
AMBIENT TEMPERATURE
STORAGE TEMPERATURE: -30
o
C to +75
o
C.
RELATIVE HUMIDITY: Operating and storage:
up to 95% (wet bulb temp. <35
o
C non-condensing).
FUSE: Slow Blow, 2A, 250V; (5 x 20 mm),
Littelfuse, P/N 215002PG;
Kepco P/N 541-0137.
DIMENSIONS: See Figure 6.
WARRANTY: 5 years.
Standard models
(no suffix)
Options
C, T, X and Y