American Dryer Corp. AD-75V User Manual

Page 29

background image

25

2. Technical Gas Data

a. Gas Specifications

Shaded areas are stated in metric equivalents

* Measured at outlet side of gas valve pressure tap when gas valve is on.

b. Gas Connections:

Inlet connection ------------- 3/4” N.P.T.
Inlet supply size ------------- 3/4” N.P.T. (minimum)
Btu/hr input (per dryer) ---- 200,000 (50,400 kcal/hr)

1) Natural Gas

Regulation is controlled by the dryer’s gas valve’s internal regulator. Incoming supply pressure
must be consistent between a minimum of 6.0 inches (14.92 mb) and a maximum of 12.0 inches
(29.9 mb) water column pressure (W.C.).

2) Liquid Propane (L.P.) Gas

Dryers made for use with L.P. gas have the gas valve’s internal pressure regulator blocked open so
that the gas pressure must be regulated upstream of the dryer. The pressure measured at each
gas valve pressure tap must be a consistent 10.5 inches (26.1 mb) water column. There is no
regulator or regulation provided in an L.P. dryer. The water column pressure must be regulated at
the source (L.P. tank) or an external regulator must be added to each dryer.

Shaded area is stated in metric equivalent

* Drill Measurement Size (D.M.S.) equivalents are as follows:

Natural Gas .......................... #29 = 0.1360” (3.4544 mm).
Liquid Propane Gas .............. #47 = 0.0785” (1.9939 mm).

NATURAL

LIQUID PROPANE

Manifold Pressure*

3.5 inches W.C.

8.7 mb

10.5 inches W.C.

26.1 mb

In-Line Pressure

6.0 - 12.0 inches W.C.

14.92 - 29.9 mb

11.0 inches W.C.

27.4 mb

Liquid

Propane

Conversion Kit

Part Number

Btu/hour

Rating

kcal/hr

Rating

Natural

Liquid Propane

Qty.

D.M.S.*

Part No.

Qty.

D.M.S.*

Part No.

200,000

50,400

4

#29

140820

4

#47

140805

882575