Gas and steam, Electrical service specifications (per dryer) – American Dryer Corp. AD-75V User Manual

Page 24

background image

20

9/22/03

IMPORTANT: 3-phase (3ø) figures shown are for a 3-wire service only.

*

AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.

9/22/03

** 3-Wire available.

b. Electric Models Only

ALL electrically heated dryers must be connected to the electric service shown on the data label. The
connecting wires must be properly sized to handle the rated current.

GAS AND STEAM

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.

C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.

Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others, calculate/verify
correct breaker size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE SIZE

FUSING

CIRCUIT

BREAKER

Dual Element

Time Delay

60 Hz

50 Hz

120

1

2

13.0

*

20

20

208

1

2

7.6

*

15

15

230/240

1

2

7.0

7.8

*

15

15

208

3

3

4.7

*

15

15

230/240

3

3

4.9

5.6

*

15

15

380

3

4**

2.9

*

15

15

400

3

4**

3.2

*

15

15

416

3

4**

3.1

*

15

15

460/480

3

3

2.8

*

15

15

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

208 VAC and 230/240 VAC ARE NOT THE SAME. When ordering, specify exact

voltage.

NOTES:

A.

B.

C.

When fuses are used they must be dual element, time delay, current limiting, class

RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local
and/or National Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others,
calculate/ verify correct breaker size according to appliance amp draw rating and type
of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

APPLIED VOLTAGE / 3 PHASE

kW

208

(60 Hz)

230/240

(50 Hz)

230/240

(60 Hz)

380

(50 Hz)

400

(50 Hz)

416

(50 Hz)

460

(60 Hz)

480

(60 Hz)

30

90

80

79

54

52

49

40

39

36

107

94

94

63

60

58

48

46

APPROXIMA

TE

AMP DRAW

2. Electrical Service Specifications

a. Gas and Steam Models Only

IMPORTANT: Figures shown are for non-reversing models only. For reversing models contact the

factory.