beautypg.com

SilentKnight VisorALARM+ Alarm Receiver over IP User Manual

Page 3

background image


Starting with default config
When you receive the device from factory it is shipped with a basic default configuration. If you wish
to defaults the device to this factory configuration use the ‘set default-config’ command.

*p 4
Config>set default-conf
All your session changes will be lost.
Activate default configuration (Yes/No)?Y
Config>

Configuring IP
Enter the following commands, substituting ip_address for the VisorALARM+ IP address, mask for
its network mask and gateway for the gateway IP address.

Config>protocol ip

-- Internet protocol user configuration --
IP config>address ethernet0/0 ip_address mask
IP config>route 0.0.0.0 0.0.0.0 gateway 1
IP config>classless
IP config>exit
Config>


Configuring the type of Alarm Receiver
Configure the udp-port for the alarm receiver. This is the receiver UDP port where the mIP devices
will send its registration and supervision data packets.

Config>network serial0/0

-- ARLY Interface Configuration --
ARLY-1 Cfg>supervision port udp-port


Parameters dependent on the emulated receiver: the commands required to configure the emulation of
the different receivers with their default parameters for communication with the automation server are
displayed below:

Sur Gard MLR-2000 / MLR2E

ARLY-1 Cfg> alarm-receiver protocol sur-gard
ARLY-1 Cfg> alarm-receiver parameters r=0
ARLY-1 Cfg> alarm-receiver receiver-id 01
ARLY-1 Cfg> alarm-receiver line-id 001


Sur Gard DLR-2

ARLY-1 Cfg> alarm-receiver protocol sur-gard
ARLY-1 Cfg> alarm-receiver parameters r=1
ARLY-1 Cfg> alarm-receiver receiver-id 01
ARLY-1 Cfg> alarm-receiver line-id 1


Radionics 6500

ARLY-1 Cfg> alarm-receiver protocol radionics-6500
ARLY-1 Cfg> alarm-receiver receiver-id 01
ARLY-1 Cfg> alarm-receiver line-id 1
ARLY-1 Cfg> alarm-receiver parameters h=0


Ademco 685: if you do not wish to use the ACK/NACK protocol, eliminate the second line.

ARLY-1 Cfg> alarm-receiver protocol ademco-685
ARLY-1 Cfg> alarm-receiver receiver-id 1
ARLY-1 Cfg> alarm-receiver line-id 1


If you need to configure another receiver or line id numbers please replace in the ‘alarm-receiver
receiver-id’ and alarm-receiver line-id’ commands the parameters that appear with identifier 1 with
your desired numbers keeping the length of the field.