140 Operators Manual

Model 140 Operator Manual

Rev. 1.8

Page 5 of 29

4.2.2

DC Power

For optional DC power input, connect 11.5-30VDC to the terminals at J8, labeled “DC IN” in Figure 3 and
Figure 4. This input can be used for primary power or back-up power in the event of a VAC power failure.

115VAC/220VAC

External

VDC

Input

VDC ON/OFF

VIN

MOTHER BOARD POWER INPUT

External

VAC

Input

J8

+

-

J2

SW4

SW1

VAC ON/OFF

F2

BATTERY
RESTORE

VSS

VIN

SW3

BATTERY
ON/OFF

SWOV

BATT2

BATT1

DC POWER
SUPPLY

TO

FRO

M

VSS

VIN

SW2

PS1

PS2

Figure 3 Power Input Schematic

4.2.3

Analog 4-20 mA Sensor Input

Connect 4-20mA type gas sensors to the motherboard at the terminal labeled “CH 1” (J15) in Figure 4.
These connections are labeled (+, -, mA). For a 3-wire gas sensor connect to the “+”, “-”, and “mA”
terminations. For a 2-wire sensor connect to the “+” and “mA” terminations, refer to the Operators Manual
for the gas sensor that is being connected.

Note: Analog sensor polling requires switch SW1-1 on the Control PCB to be set in the “OFF” position.
(See Figure 5)