beautypg.com

0 maintenance & repair, 1 start up – Detcon 610-N4X-SA User Manual

Page 10

background image

Model 610-N4X-SA

6. Each alarm has an associated set of dry contacts from the Alarm/Fault relay’s (Figure 3 and Figure 5).

These dry contact terminals consist of a Common relay connection through a terminal disconnect, and
the NC and NO Contacts via through terminals (Figure 4).

24 25 26

CO

M

NC

NO

Disconnect Terminal Block

Through Terminal Block

COM - Common

NC - Normally Closed
NO - Normally Open

Figure 5 Typical Dry Contact Connections

7. If applicable, connect a 24VDC source or standby battery to the terminal strip labeled “VDC IN” (+

and –) on the Motherboard (Figure 2).

8. Connect 117VAC input to the Circuit Breaker labeled “VAC IN” in the lower left of the enclosure

(Figure 3 and L1, N, EARTH in Figure 6). If applicable, connect 220VAC. The power supply will
accept both voltages.

9. Connect Earth Ground to Terminal TB1-1, and Neutral to terminal TB1-5 (Figure 6).

7

8

9

5

6

1

2

3

G

rou

nd

/

Ear

th

V

A

C

In

pu

t /

L1

Ne

ut

ra

l /

N

20Amp

Brkr

4

ON

Figure 6 Input Power Connections

2.1 Start

Up

Upon completion of all field wiring: Apply power to the 610-N4X-SA by turning the 20Amp Circuit Breaker
ON. Note that each Model 10 controller digital display illuminates. Note; varying readings may occur during
sensor warm-up. A 10 second alarm delay will occur on power up. Refer to the applicable Sensor Instruction
Manual for additional sensor start-up details.

3.0 Maintenance & Repair

The Detcon Model 610-N4X-SA’s modular design allows for minimum ‘down-time’ during maintenance
and/or repair.

610-N4X-SA Instruction Manual

Rev. 0.1

Page 6 of 8