4 Channel Relay Card

Four Channel Relay Card Instruction Manual

Rev.1.2

Page 6 of 8

4.0Troubleshooting Guide

Problem

Potential Cause(s)

Fault active

More than 3 alarm levels are set on an active channel
No alarm levels are set on an active channel
4-20mA input is not connected to the Channel
4-20mA input is below 2.2mA – fix/replace sensor

Sensors not receiving power

Sensor not connected correctly
Input voltage to Relay Card is not correct level (12-28 VDC)
Connector wired incorrectly

Alarm Relay Active when sensor(s) is not in
alarm

Relay is set for energized
Relay connector wired incorrectly

For further troubleshooting assistance, contact Detcon Service Department at

[email protected]

, or contact

Detcon customer service.

5.0Specifications

Capacity

Up to 4 4-20mA input devices

Indicators:

Power Indicator LED
3 Alarm Status LED’s
1 Fault Status LED
Channel Indicator LED’s

Detection Accuracy

+/2 2% of full scale value between 10% and 60%

Input Options:

Analog 4-20 mA DC

Output Options

Programmable Relay Contacts

Relays rated 5A @ 30VDC/250VAC

Warranty

One Year

Mechanical Specifications

Dimensions 4.5” x 5”

Electrical Specifications

Power Consumption

12-28VDC @ 800 mA max (Including Sensors)

5.1 Parts List

Part Number

Description

306-177984-800

3-Pin Connector

306-175701-900

2-Pin Connector

440-005155-000

Four Channel Relay Card