Installation, Figure 3 sstx-mv printed circuit board, 0 installation – Detcon AV2-C1D2M User Manual
Page 7

AV1/AV2-C1D2M
Height 14.75in.
Width 8.88in.
Long 14.75in
Sound Selectable Positions Listed in Figure 3
Figure 3 SSTX-MV printed circuit board
2.0 Installation
The assembly is mounted on a T-shaped Aluminum bracket with holes pre-drilled to accommodate (2) U-bolt
attachments on a 2.5” maximum diameter pipe. U-bolt size is 3/8-16 x 3 inches. Overall Dimensions are
33”H x 16.5”W x 18.5”D (Figure 4).
The tone for the siren is set using tone selector jumpers, J4 & J5. Each jumper consists of three pins and the
selection of appropriate tone is made by placing a jumper on two of the three pins as shown in
The alarm comes pre-wired for the voltage ordered from the factory (110/220VAC or 24VDC). Wiring is
installed through the opening at bottom of junction box. Connect wiring in accordance with the appropriate
wiring diagram (Figure 6 or Figure 7), AV1-C1D2M being wired for Strobe 1 only. Use only 12 to 18 AWG
wire for power connections. Strip no more than 0.25-inch of insulation from the ends of the power leads.
AV1/AV2-C1D2M Instruction Manual
Rev. 2.1
Page 3 of 8