beautypg.com

Flow fault circuit, Flow fault contacts, 2 start up – Detcon 971-071170-00L User Manual

Page 4: 3 flow fault detection

background image

7. If applicable, connect alarm devices. Discreet alarm relay contacts are provided for three alarms: Fault,
Low and High. The contacts consist of common and choice of normally open or normally closed. Contact
output selections are jumper programmable on the sensor connector board. See the sensor manual for con-
tact ratings and other information.
8. If applicable, connect flow fault alarm wiring. Two sets of form C contacts (common, normally open and
normally closed) are provided. Relay contacts are rated 1 amp at 30VDC/.24 amp at 125VDC.
9. If applicable, connect RS-485 wiring.

The RS-485 requires 24 gauge, two conductor, shielded, twisted pair

cable between sensor and host PC. Use Belden part number 9841. Two sets of terminals are located on the
connector board to facilitate serial loop wiring from sensor to sensor. Wiring designators are +, –, and shield.

1.2 START UP

Upon completion of all tubing connections and field wiring turn on the power switch located on the enclo-
sure door. Note that the power lamp illuminates. If applicable, note that the sensor LCD indicator activates.
Varying readings may occur during sensor warm-up. Allow approximately 1 hour to stabilize (24 hours is best).

Also note air flow through the flow meter. Adjust the flow meter as necessary so that it falls between 500
and 1000 ml/m (milli liters per minute).

Assure that all field tubing connections are secure by obstructing the end of the sample line and observ-

ing that the flow meter decreases to “0” flow.

1.3 FLOW FAULT DETECTION

Flow fault detection consists of a flow fault circuit assembly located inside the enclosure and a door mount-
ed fault indicator lamp. If the air flow falls below a predetermined set point the following will occur: the
flow fault alarm relays will energize; an LED indicator mounted on the flow fault PCB will illuminate; the
door mounted flow fault lamp will illuminate; the 4-20mA signal will be opened via relay #1 on the flow

Detcon Model 971-071170-00L Gas Detection System PG.4

P7

P8

P6

P5

L1 L2 GND

mA

C NO/NC C NO/NC C NO/NC

117 VAC

IN

24 VDC

IN

Battery

Backup

SENSOR #1

FAULT

ALARM CONTACTS #1

ALARM 1 ALARM 2

ALARM DRY

CONTACTS

COM

NO/NC

COM

COM

NO/NC

NO/NC

FLT ALM 1 ALM 2

Flow

Fault

Circuit

COM

NO

NC

1

COM

NO

NC

2

COM

NO

NC

3

PT1

mA

4-20mA

Wire alarms and the 4-20mA output
signal to the plug-type connectors.

Wire 117 VAC & optional 24 VDC
backup to the lugless connectors.

Two discreet form C dry contacts
are provided (2 & 3) by the flow
fault circuit for alarm devices. The
first set of contacts (1) are
prewired to interrupt the 4-20mA
signal output in the event of a
flow fault. This will allow for flow
fault monitoring at any
controller/computer that the signal
is wired in to.

FLOW

FAULT

CONTACTS