3.0 Operation
The SW-AV1-N4 Wireless Alarm Stations provides a strobe and a horn. The wireless alarm station is set to
respond to alarms from the controlling unit via the RXT-320 transceiver. The controller/wireless network has
independent control over the strobes and the Horn, and they will be activated when the appropriate alarm is
activated, via the RL4 Module.
The unit needs to have both the Transceiver and the RL4 configured before the unit will operate properly. To
do this the RL4 Modbus™ address must correspond to the setting of the controller, and the transceiver address
must be set properly for the transceiver to be recognized on the network. Refer to the Controller Manual for
more information.
The horn has up to 32 possible settings, for use in different configurations. The default settings of the horn are
factory set. To change the setting of the horn, remove the rear end of the horn, and set the dip switches
according to the Sound Signals Table.
Table 1 Sound Signals
TONE FREQ/DESCRIPTION
SWITCH
TONE
1
Alt Tones 800/970 Hz at 1/4 sec
11111
2
Sweeping 800/970 Hz at 7Hz
11110
Fast Sweep(LF)
3
Sweeping 800/1000 Hz at 1 Hz
11101
Med Sweep(LF)
4
Continuous at 2850 Hz
11100
5
Sweeping 2400-2850 Hz at 7 Hz
11011
Fast Sweep
6
Sweeping 2400-2850 Hz at 1 Hz
11010
7
Slow Whoop
11001
Slow Whoop
8
Sweep 1200-500 Hz at 1 Hz
11000
Din Tone
9
Alt. Tones 2400/2850 Hz at 2 Hz
10111
10
Int. Tone of 970 Hz at 1 Hz
10110
Back-Up Alarm(LF)
11
Alt. Tones 800/970 Hz at 7/8 Hz
10101
12
Int. Tone at 2850 Hz at 1Hz
10100
Back Up Alarm(HF)
13
970Hz at 1/4 sec on 1 sec off
10011
14
Continuous at 970 Hz
10010
15
554Hz for 100ms / 440 Hz for 400ms
10001
French Fire Sound
16
Int. 660 Hz 150 ms on 150 ms off
10000
Swedish Fire Alarm
17
Int. 660 Hz 1.8 sec on 1.8 sec off
01111
Swedish Fire Alarm
18
Int. 660 Hz 6.5 sec on 13 sec off
01110
Swedish Fire Alarm
19
Continuous 660 Hz
01101
Swedish Fire Alarm
20
Alt 554/440 Hz at 1 Hz
01100
Swedish Fire Alarm
21
Int. 660 Hz at 7/8 Hz
01011
Swedish Fire Alarm
22
Int. 2850 Hz 150 ms on 100 ms off
01010
Pelican Crossing
23
Sweep 800-970 Hz at 50 Hz
01001
Low Freq. Buzz
24
Sweep 2400-2850 Hz at 50 Hz
01000
High Freq. Buzz
25
3 970Hz pulses 0.5on/0.5off, 1.5 off
00111
26
3 2850Hz pulses 0.5on/0.5off, 1.5 off
00110
27
Int. 3100 Hz 0.32s on / 0.68s off
00101
28
Spare/Customer Tone
00100
29
Spare/Customer Tone
00011
30
Spare/Customer Tone
00010
31
Spare/Customer Tone
00001
32
Spare/Customer Tone
00000