beautypg.com

Detcon 1212-N4X User Manual

Page 7

background image

1.6 I

NSTALLATION

1. Securely mount the 1212-N4X enclosure in accordance with the drawing in f igure 5.

Note: Reference f igure 6 for wiring terminations.

Caution: Observe correct polarity when terminating all input/output field wiring. Failure to do so may result in

circuit damage on power up.

2. Connect 85-264 VAC input to the terminal strip labeled “VAC IN” (L1, N, GND).

3. If applicable, connect a 24VDC source or standby battery to the terminal strip labeled “VDC IN” (+ and –).

4. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0. Terminate

f ield wiring from sensors to the 1212-N4X motherboard. Terminals are labeled “Sensor” (mA, + and –).

5. If applicable, terminate the discrete 4-20 mA outputs to external device(s). Terminals are labeled “4-20mA Out”

(+ and –).

6. If applicable, terminate the RS-485 serial output to external device(s). Terminals are labeled “RS-485” (A+, B–,

and Shield). RS-485 outputs may be common or zoned (up to two zones) via the gold-plated jumper tabs.

7. Based on the application and use of relay contact outputs, complete all wiring terminations prior to application

of power. Shut-in controls may be omitted until system test is complete. Terminals are labeled “ALARM 1”

(Com & NO/NC), “ALARM 2” (Com & NO/NC), “ALARM 3” (Com & NO/NC), and “Fault” (Com &

NO/NC). Relay contact outputs may be discrete or zoned via the gold-plated jumper tabs. Relay contact outputs

may be used in conjunction with the multiple alarm relay circuit as described in section 1.3.

Model 1212-N4X NEMA 4 Control Enclosure PG.7

23.07

14

20.63

Mounting Holes - 7/16" Dia.

10.25

21.81

Figure 5