Detcon 1212-N4X User Manual

Page 2

background image

Table of Contents

1.0

Introduction

1.1

Description

1.2

Specifications

1.3

Multiple Alarm Relay Circuit

1.4

Alarm Disable

1.5

Remote Alarm Reset

1.6

Installation

1.7

Start-up

1.8

Maintenance & Repair

1.9

Spare Parts List

1.10

Warranty

1.0 I

NTRODUCTION

Detcon Model 1212-N4X consists of 3 major assemblies:

1. The NEMA 4 f iberglass control enclosure.

2. The Model 12 single channel digital control modules.

3. The remote mount gas sensor assemblies.

The NEMA 4 control enclosure is detailed in section 1.0 of the manual, the control modules in section 2.0, and

applicable sensor assemblies in section 3.0.

1.1 D

ESCRIPTION

Detcon Model 1212-N4X control enclosure, along with Model 12B digital control modules, is designed to serve as a

host assembly for up to twelve remote mount gas detection sensor assemblies. The control enclosure is rated

NEMA 4X, which is by def inition rain tight, and therefore suitable for outdoor location in electrically non-haz-

ardous environments.

The single channel modular design supports application f lexibility wherein multiple function gas detection systems

can be conf igured in any combination up to twelve channels. All control modules are plug-in front panel accessible

for easy maintenance and repair. The system is powered by VAC line power and/or 24VDC unless otherwise speci-

f ied at time of order.

The control enclosure includes, as standard operating controls; a power on/off switch, an alarm disable switch and

a line power fuse. Discrete output terminal strips located on the controller motherboard are provided for sensor ter-

minations, Form C dry contact alarm outputs for three alarms plus fault (common and choice of normally open or

normally closed), 4-20 mA outputs for remote recording devices, and RS-485 serial Modbus™ output. Terminations

are provided for VAC power in, VDC power in, and remote alarm reset. A multiple alarm relay circuit card is also

provided along with its respective logic and power terminations.

The RS-485 serial output, as well as the Form C relay outputs, may be discrete, zoned, or common by gold plated

jumper tabs located on the controller mother board.

Model 1212-N4X NEMA 4 Control Enclosure PG.2