beautypg.com

Detcon 1212-N4X User Manual

Page 3

background image

1.2 S

PECIFICATIONS

Electrical Classification

NEMA 4X

Dimensions

20.25''W x 20.19''H x 10.25''D

Capacity

12 single channels

Power Input

85-264 VAC/24VDC

Power Consumption

5 watts per channel (full alarm peak load)

Outputs

Discrete Analog 4-20 mA DC

Discrete or zoned (up to two) Serial RS-485 Modbus™

Discrete or zoned alarm relays

Contacts include common with jumper selectable choice (on controller) of normally-open or normally-closed for four alarms

Resistive load: 5A, 250 VAC; 5A, 30 VDC

Inductive load: 2A, 250 VAC; 2A, 30 VDC

Max. operating current: 5A

Operating Temperature Range

-40°F to +175°F

Warranty

One year

1.3 M

ULTIPLE

A

LARM

R

ELAY

C

IRCUIT

A multiple alarm relay circuit (referred to in further text as MARC) mounted on the controller mother board is

provided with each Detcon Model 1212-N4X. The MARC (f igure 1) consists of 4 interposing relays (contacts are

rated 10 amp @ 120 VAC/8 amp @ 30 VDC) with 24VDC coils as standard. Other coil voltage ratings must be

specif ied at time of order. The MARC can be conf igured to output Form C dry contacts (common, normally open

and normally closed), AC power or DC power. A 5 amp microfuse is provided for each relay and is conf igured in

series with the common pole of its respective relay. This conf iguration is functional regardless of whether Form C

dry contacts, AC power or DC power outputs are used.

An in/out termination is provided for applying AC or DC power into any one of the interposing relays. A gold

plated jumper tab is used to apply the in/out power option to its corresponding relay, thus the 4 relays may be

used in a combination of Form C dry contacts and DC outputs or Form C contacts and AC outputs.

The terminations labeled “Alarm Coil Power” located on the left of the 1212-N4X motherboard are used only for

coil power. The “+” termination may be used to provide for various relay logic through the Form C dry contacts

terminals of each individual Model 12B channel located on the 1212-N4X motherboard. The “–” termination

should be wired into the common terminal (shown by a common symbol) located on the left of the MARC.

The terminations labeled “Alarm Power” located on the left of the 1212-N4X motherboard are used for providing

power to the In/Out termination on the MARC. As can be seen in the 1212-N4X schematic/wiring diagram (f igure

2), the alarm power terminations for AC come directly from the AC input terminals located above on the 1212-

N4X motherboard. The same is true of the DC power terminations.

Note: DC power used to drive alarms must be obtained through a remote DC power source. The remote DC

power source should be terminated to the terminals labeled “DC IN” located on the 1212-N4X motherboard. The

“DC IN” terminations function as both an alternative DC source used to power the 1212-N4X as well as provide

power for DC alarms. The 1212-N4X power supply is not capable of providing power for alarm devices.

Mounting hardware is pre-installed on the 1212-N4X motherboard for an additional multiple alarm relay circuit. See

section 1.9 for part number and ordering information.

Model 1212-N4X NEMA 4 Control Enclosure PG.3