Field wiring, Figure 13 typical installation, Figure 13 – Detcon FP-100 User Manual

Page 14: Figure 13, the drain allows h, 6 field wiring

background image

Model FP-100

FP-100 Instruction Manual

Rev. 0.0

Page 10 of 30

Drain

Conduit

"T"

EYS Seal Fitting

DETCON, INC.

LEL

100 %

FP-100

Model 100

Figure 13 Typical Installation

NOTE: Any unused ports should be blocked with suitable ¾” male NPT plugs. Detcon
supplies one ¾” NPT male plug with each J-box enclosure. If connections are other than ¾”
NPT, use an appropriate male plug of like construction material.

2.6 Field Wiring


Detcon Model FP-100 sensor assemblies are designed to connect to a host electronic controller’s 4-20mA
input. Wiring designations are ‘PWR’, ‘GND’ and ‘MA’ (sensor signal). The maximum wire size for
termination in the Junction Box is 14 AWG.

NOTE 1: Shielded cable is required for installations where cable trays or conduit runs include
high voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.

NOTE 2: The supply of power should be from an isolated source with over-current protection.


Terminal Connections – with Junction Box Option

CAUTION: Do not apply System power to the sensor until all wiring is properly terminated. Refer
to Section 2.7 Initial Start Up


1. Remove the junction box cover.

2. If the sensor has the 100 Series Display option installed, unplug the display from the terminal board by

pulling the display out of the junction box. The display option plugs directly into the terminal board’s
Beau Connector.