Detcon TP-524C User Manual
Page 6
3.3 S
PECIFICATIONS
Method of Detection
Solid state metal oxide diffusion/adsorption
Electrical Classification
CSA-NRTL (US OSHA) approved Class I; Groups B, C, D; Div. 1.
Response Time
T50 < 30 seconds, T80 < 60 seconds
Clearing Time
T80 < 30 seconds
Repeatability
± 10% of reading or ± 2 ppm (greater of)
Range
0-20 ppm, 0-50 ppm, or 0-100 ppm
Operating Temperature
-40° to +175° F (-40°C to +75°C)
Accuracy
± 10% of reading or ± 2 ppm (greater of)
Sensor Warranty
10 year conditional
Power Consumption
Normal operation = 68 mA (<1.7 watt); Full alarm = 85 mA (2 watts)
Output
Linear 4-20 mA DC
Input Voltage
12-28 VDC
3.4 O
PERATING
S
OFTWARE
Operating software is menu listed with operator interface via the two magnetic program switches located under the
face plate. The two switches are referred to as “PGM 1” and “PGM 2”. The menu list consists of 3 items which
include sub-menus as indicated below. (Note: see the last page of this manual for a complete software f low chart.)
01.
Normal Operation
a) Current Status
02.
Calibration Mode
a) Span
03.
Program Menu
a) View Program Status
b) Set Calibration Level
c) Set Heater Level
d) Set Range
e) Utility Menu
3.4.1 Normal Operation
In normal operation, the display ref lects the current status of the sensor and gas concentration and appears as:
“0 PPM H2S”
. The mA current output corresponds to the monitoring level and range of detection = 4-20 mA.
3.4.2 Calibration Mode
Detcon Model TP-524C Hydrogen Sulfide Sensor
PG.6