6 field wiring – Detcon FP-624D-HT User Manual
Page 14
Model FP-624D-HT
FP-624D-HT Instruction Manual
Rev. 1.1
Page 10 of 44
Figure 9 Typical Installation
NOTE: Any unused ports should be blocked with suitable ¾” male NPT plugs.
Detcon
Supplies one ¾” NPT male plug with each J-box enclosure. If connections are other than ¾”
NPT, use an appropriate male plug of like construction material.
2.6 Field Wiring
Detcon Model FP-624D-HT High Temperature combustible gas sensor assemblies require up to five conductor
connections between power supplies and host electronic controller. Wiring designations are DC+, DC-, MA
(sensor signal), Modbus A and Modbus B.
If the MA signal is not needed, its terminal may be left
unconnected.
A 250 ohm load resistor is needed on the 4-20 mA line when it is not being used.
The
maximum wire length between sensor and 24VDC source is shown in the Table below. The maximum wire
size for termination in the Junction Box is 14 AWG.
Table 1 Wire Gauge vs. Distance
AWG
Wire Dia.
Meters
Feet
Over-Current
Protection
22
0.723mm
700
2080
3A
20
0.812mm
1120
3350
5A
18
1.024mm
1750
5250
7A
16
1.291mm
2800
8400
10A
14
1.628mm
4480
13,440
20A
NOTE 1: Wiring table is based on stranded tinned copper wire and is designed to serve as a
reference only.
NOTE 2: Shielded cable is required for installations where cable trays or conduit runs include
high voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.
NOTE 3: The supply of power should be from an isolated source with over-current protection
as stipulated in Table 1 Wire Gauge vs. Distance.
NOTE 4: A 250 ohm load resistor is needed on the 4-20 mA line when it is not being used.
Drain
Conduit
"T"
EYS Seal Fitting