5 electrical installation, Figure 8 typical outline and mounting dimensions – Detcon FP-624D-HT User Manual

Page 13

background image

Model FP-624D-HT

FP-624D-HT Instruction Manual

Rev. 1.1

Page 9 of 44

Figure 8 Typical Outline and Mounting Dimensions

2.5 Electrical Installation

The Sensor Assembly should be installed in accordance with local electrical codes. The sensor assemblies are
CSA/NRTL approved (US and Canada) for Class I, Division 1, Groups B C D area classifications.

Proper electrical installation of the gas sensor is critical for conformance to Electrical Codes and to avoid
damage due to water leakage. Refer to Figure 9 and Figure 8 for proper electrical installation.

NOTE: If a conduit run exits the secondary port, repeat the installation technique shown in
Figure 9.

In Figure 9, the drain allows H

2

O condensation inside the conduit run to safely drain away from the sensor

assembly. The electrical seal fitting is required to meet the National Electrical Code per NEC Article 500-3d
(or Canadian Electrical Code Handbook Part 1 Section 18-154). Requirements for locations of electrical seals
are covered under NEC Article 501-5. Electrical seals also act as a secondary seal to prevent water from
entering the wiring terminal enclosure. However, they are not designed to provide an absolute watertight seal,
especially when used in the vertical orientation.

NOTE: A conduit seal is typically required to be located within 18" of the J-Box and Sensor
Assembly. Crouse Hinds type EYS2, EYD2 or equivalent are suitable for this purpose.

NOTE: The Detcon Warranty does not cover water damage resulting from water leaking into
the enclosure.

External Ground Screw
8-32 x 5/16" binding
head screw

3

4

NPT Ports

1

4

" mounting holes

2"

2.1"

0.5"

W

a

ll

(o

r

o

th

e

r

m

o

u

n

ti

n

g

s

u

rf

a

c

e

)

Splash Guard

High Temperature
LEL Sensor

5.825"

5.5"

6.1"

4.65"