beautypg.com

Detcon DM-600IS User Manual

Page 35

background image

DM-600IS

DM-600IS Instruction Manual

Rev 1.5.9

Page 31 of 37

declassification of the area would be required. See section 5.4-f) for details on changing the RS-485 ID
number.

The following section explains the details of the Modbus™ protocol that the MicroSafeTM sensor supports.

Code 03 - Read Holding Registers is the only code supported by the transmitter. Each transmitter contains 6
holding registers which reflect its current status.

Register #

High Byte

Low Byte

0000

Gas type

Sensor Life

Gas type is one of the following:
01=CO, 02=H2S, 03=SO2, 04=H2, 05=HCN, 06=CL2, 07=NO2, 08=NO, 09=HCL, 10=NH3, 11=LEL,
12=O2

Sensor life is an estimated remaining use of the sensor head, between 0% and 100% Example: 85=85% sensor
life

Register #

High Byte

Low Byte

40001

Detectable Range

i.e. 100 for 0-100 ppm, 50 for 0-50 ppm, etc.

Register #

High Byte

Low Byte

40002

Current Gas Reading

The current gas reading as a whole number. If the reading is displayed as 23.5 on the display, this register
would contain the number 235.

Register #

High Byte

Low Byte

40003

Alarm 1 Set point

This is the trip point for the first alarm.

Register #

High Byte

Low Byte

40004

Alarm 2 Set point

This is the trip point for the second alarm.

Register #

High Byte

Low Byte

40005

Status Bits

Status Bits

High Byte
Bit 7

Not used, always 0

Bit 6

Not used, always 0

Bit 5

Not used, always 0

Bit 4

Not used, always 0

Bit 3

1-Unit is in calibration

0-Normal operation

Bit 2

1-Alarm 2 is ascending

0-Alarm 2 is descending

Bit 1

1-Alarm 2 is normally energized

0-Alarm 2 is normally de-energized

Bit 0

1-Alarm 2 is latching

0-Alarm 2 is non-latching