Figure 8 Jumper Tab Positions on Term Board

Note: If a voltage signal output is desired in place of the 4-20mA output, a 1/4 watt resistor

must be installed in position R1 of the terminal board. A 250

resistor will provide a 1-5V

output (– to mA). A 100

resistor will provide a .4-2V output, etc. This linear signal

corresponds to 0-100% of scale (see Figure 8).

e) Program the alarms via the gold plated jumper tab positions located on the CPU board (see Figure 9).

Alarm 1 and Alarm 2 have three jumper programmable functions: latching/non-latching relays,
normally energized/normally de-energized relays, and ascending/descending alarm set points. The
fault alarm has two jumper programmable functions: latching/non-latching relay, and normally
energized/normally de-energized relay. The default settings of the alarms (jumpers removed) are
normally de-energized relays, non-latching relays, and alarm points that activate during descending
gas conditions.

Figure 9 Alarm Programming Jumpers