beautypg.com

AW Gear Meters FIP User Manual

Fip analog output sensor

background image

AW-Lake Company 8809 Industrial Drive, Franksville, WI 53126  web: www.awgearmeters.com

 Tel: 262-884-9800  Fax: 262-884-9810  Email: [email protected]

REV. 12/12 FIP Sensor.DOC

FIP Analog Output Sensor


The FIP is a microprocessor based, meter mounted, analog output sensor. Each unit has a
sensor, amplifier and converter module built into an aluminum junction box. The FIP is designed
to handle frequencies up to 5,000 Hz. The operational frequency range is user defined via four
BCD rotary switches, where the high flow rate in frequency is set to 20 mA, 5V or 10V, and the
out

put signal is automatically scaled. End connection options include ½” NPT for running conduit

piping, or a 3-pin connector.

NOTE: This is a 3 wire hookup and is not suitable for a 2 wire installation.



















Ordering Information

FIP X X X

S: 3-Pin Connector

E: Conduit Connection


Meter Selection

H: JV, HPM, TRG Series

T: TR-1100 Series

IR: JVK Series


Output

1: 1-5 V

2: 2-10V

4: 4-20 mA

5: 0-5V

10: 0-10V

20: 0-20 mA

Technical Specifications

Supply Voltage: 10-30 VDC

Supply Current: 60 mA max

Signal Output: 0-20 mA, 4-20mA or

0-5V, 0-10V, 1-5V, 2-10V

Max Load Impedance

(Vcc/0.02) – 275 ohm (for mA out)

Min Load Impedance:

500 ohm (for Volt out)

Driving Capacity:

For Voltage output only 10 mA max

Temperature Range:

0-185° F

Jumper Settings

J1

AB: Analog Output

BC: Frequency Output

J2

AB: Housing Ground

CB: Signal ground

Response Time: 1/F + 25 msec

Frequency Input: 5 KHz max
Diagnostics:

A glowing LED indicates the unit is working.

The LED will blink to show an active
frequency.