beautypg.com

Installation, Electric shock can kill, Connection for negative polarity welding – Lincoln Electric IM697 RED-D-ARC MX 300 User Manual

Page 14: Power source setup, Warning, Caution

background image

A-7

INSTALLATION

A-7

RED-D-ARC MX350

Table .1

Converters

Cable Size

on Cable

AWG (mm2 )

1

1/0 (50)

2

2/0 (70)

3

3/0 (95)

4

4/0 (120)

5

2x3/0 (2x95)

The output "Electrode" cable should be 2/0 AWG
(70mm

2

) if sized for rated output up to 200 ft.(61m)

from the Converter. If paralleled, the output cable to
the arc should be 4/0(120mm

2

).

ELECTRIC SHOCK can kill.

Do not disconnect the Work clip lead
without first switching OFF the
Converter panel switch. Failure to do
so will allow the work lead clip to be
electrically "hot" to work, and "hot" to
the electrode, through the circuit of

the Converter for about 5 seconds until the input
contactor opens.

------------------------------------------------------------------------

CONNECTION FOR NEGATIVE
POLARITY WELDING

(See Figure 2A)

A RED-D-ARC MX350 may be used for Negative
(straight) polarity CV (Innershield) or CC processes if
connected per the diagram shown below:

No more than one RED-D-ARC MX350 may be
connected to a power source for Negative Polarity
welding. Multiple units connected to the same
power source may cause damage to the RED-D-
ARC MX350.

------------------------------------------------------------------------

This connection method will only permit using one
RED-D-ARC MX350 arc on one power source, and
cables have to be run to the RED-D-ARC MX350 from
both (+) and (-) output studs of the power source. This
is required so that the (-) electrode has a return path
to both the RED-D-ARC MX350 and the Power
Source, just like the normal (+)polarity connection has
a (-) return path to both the RED-D-ARC MX350
(through the Work Clamp) and to the Power Source
(through work connections). Both cable sizes are the
same, with capacity as recommended for normal (+)
connection.

If the power source itself can not perform the CV
negative welding process, the RED-D-ARC MX350 is
basically serving very well as a process converter (ei;
CV from a CC power source), as well as a remote
output control. The advantage is that the same
equipment (RED-D-ARC MX350ʼs and CC Power
Sources) are used for all weld process applications.

POWER SOURCE SETUP

Refer to the Instruction Manual provided with the
Multi-Source power source, or other DC power source
being used, for input power supply connections,
output connections and controls setup.

In general:

1. Connect the positive (+) output connection terminal

to the input supplying the RED-D-ARC MX350 sys-
tem, and the negative (-) output connection termi-
nal to the work. (see Figure 1).

2. If not using a Multi-Source power source;

a If an inductance control, or tap, is selectable,

use lowest inductance.

b. Use CC (Constant Current) mode, for maximum

supply voltage.

c. Set panel output control to maximum, for maxi-

mum current capacity.

d. Activate output with the "output terminals on"

switch, or jumper (2-4 on LE Co terminal strips).

WARNING

-

+

W

Wor

ork

Wor

ork

LN-25 Wire

LN-25 Wire
Feeder

Feeder

W

Wor

or k

(-)

(-) Work Lead

ad

t o

(-)

(-) P

Pow

ower

r Sou

ourc

rce s

stu

tud

and

nd

(-)

(-) Electrode Lead

Electrode Lead

MX350

MX350

MX350

MX350

(+)

) Out pu

put Lea

Lead

to

o W ork

MX350

MX350

Negative Polarity

Negative Polarity

DC

DC

POWER

POWER

SOURCE

SOURCE

CAUTION

Figure 2A