PROBLEM:
UPS does not provide expected back up time.
Possible cause:
UPS’s battery is weak from recent outage or wear.
Solution:
The battery needs recharging after an extended
outage. The battery wears faster when put into service
often and when used at higher temperatures.
Possible cause:
UPS is overloaded.
Solution:
Check load using UPS’s output power bar graph (see
Sec. 5.2). Unplug non-critical equipment and printers.
PROBLEM:
Indicators on front panel flash in a “marquee” fashion.
Possible cause:
UPS has been shut down by computer software.
Solution:
UPS will restart when AC power returns.
PROBLEM:
All indicators are lit and UPS emits constant tone.
Possible cause:
Internal UPS fault.
Solution:
Do not attempt to use UPS. Turn off UPS and have it
serviced immediately.
PROBLEM:
Site wiring fault light is lit—UPS operates normally.
Possible cause:
Building wiring error such as missing ground or hot-
neutral reversal.
Solution:
A qualified electrician should be summoned to correct
the building wiring.
PROBLEM:
Replace Battery indicator is lit.
Possible cause:
Weak battery.
Solution:
Allow the battery to recharge for at least 8 hours. If
the problem persists after recharging, the battery
should be replaced.