0 difficulty – APC 600 User Manual
Page 33

31
7.0 Difficulty
7.1 Troubleshooting
PROBLEM:
UPS will not turn on
Possible cause:
UPS Enable switch is in the off position or the power
on switch is not pressed.
Solution:
Turn on the rear panel UPS Enable switch. Press front-
panel power on switch to energize UPS and loads.
Possible cause:
UPS’s circuit breaker is tripped (button is extended).
Solution:
Reduce the UPS’s load by unplugging equipment and
reset the circuit breaker (press button on rear panel).
Possible cause:
Very low utility voltage or dead outlet.
Solution:
Check outlet with a table lamp. If very dim, have
utility voltage checked by an electrician.
PROBLEM:
UPS operates on-battery even though normal line
voltage is thought to exist.
Possible cause:
UPS’s circuit breaker is tripped (button is extended).
Solution:
Unplug equipment to reduce the UPS’s load. Press the
button on the rear panel to reset circuit breaker.
Possible cause:
Very high, low, or badly-distorted line voltage.
Solution:
Test the input voltage with UPS’s line voltage bar
graph (see Sec. 5.3). Inexpensive fuel powered
generators can cause distorted line voltages—set
Option Switch 1 to the on (
I
) position.
PROBLEM:
UPS “beeps” occasionally.
Possible cause:
This is normal; the UPS is protecting your computer
equipment from momentary sags or swells.
PROBLEM:
UPS beeps more than once or twice an hour.
Possible cause:
Chronically high or distorted line voltage.
Solution:
Set Option Switches 1 and 2 to match input voltage
range. Alternatively, set Option Switch 3 to the on (
I
)
position (see Sec. 5.5).