Checking and replenishing tank air charge, Periodic checks – Davey SUPERCELL 60F, 80F, 100F, 130F, 200F, & 250F PRESSURE TANKS User Manual
Page 4
- 4 -
- 5 -
Checking and Replenishing Tank Air Charge
Supercell “F” Pressure Tanks do not require regular air checks under normal
operating conditions. If air charge adjustment is required then follow the
following procedures:
1. Remove the pressure tank completely from pump installation, ensuring
to isolate the pressure tank and release the water pressure from the tank
beforehand.
OR
Release all water pressure from the pressure tank by switching off the pump
at the power point, and opening the closet tap. For above ground supply
tanks it is necessary to close the gate valve between the supply tank and the
pump.
Leave tap open during air replenishment.
2. When all water pressure has been released from the system, check air
pressure at air valve on top of pressure tank. The pre-charge pressure
reading should be as detailed on page 3 of this document.
3. If necessary, replenish air charge to the correct pressure indicated. Ensure
that a tap in outlet piping of pump is open during replenishment of air pre-
charge.
Periodic Checks
Flushing: Depending on the quality of the pumped water, from time to time
your tank may require flushing to remove settled fines such as mud or sand. If
sand or mud is allowed to stay in the tank it will accelerate wear on the internal
lining and shorten your tanks life.
Safely disconnect the tank from the water supply, discharge all air from the tank
and flush the tank several times with clean water. Once the flushing water is
clean, reconnect the tank and recharge the air as per above.
External Inspection: A tank in good order will not leak, but over time due
to damage through rough handling, impacts or grit and/or impurities in the
water the tank shell may fail and/or leak. Should the tank leak or show signs of
possible failure the tank should be immediately disconnected and replaced.
CAUTION: To prevent personal injury, ensure all water pressure is
released from the pressure system prior to work being performed.
NOTE: During air replenishment the tank should be externally
inspected. Any signs of leakage from the tank may indicate a need for
immediate replacement.
WARNING: Do not use tank if it leaks or shows signs of corrosion or
damage.
Operational Difficulties & Trouble Shooting
NOTE:
Loss of air charge is the most overwhelming cause of difficulties with
Supercell Pressure Tanks. Partial or complete loss of air charge will
cause any of the following problems:-
a) Rapid pump cycling (ie. pump stops and starts frequently during
operation).
b. Decreased draw-off capacity.
Alternatively, the same problems could be caused by a punctured or
leaking diaphragm as indicated by water leaking from the air valve
when the valve core is depressed (typically when checking tank pre-
charge).
Supercell 60F, 80F, 100F, 130F, 200F and 250F have a diaphragm
which is captive (non-serviceable). In the event of diaphragm failure
the whole tank must be replaced.
Symptom Causes
Remedies
Pump Cycling
i) Punctured diaphragm (check that water i) Replace Tank.
(Pump stops and starts
escapes from air valve when depressed)
frequently while operating) ii) Incorrectly set pressure switch
ii) Reset pressure switch to manufacturers
recommendations
iii) Incorrect pressure tank pre-charge
iii) Adjust tank pre-charge to 15kPa (2psi)
below
cut-in
Pump stops and starts
i) Leaking tap or pipework on suction
i) Isolate suction pipework, if pump
when all taps are closed
and/or discharge side
continues to stop and start, check for
leaks on discharge. If pump stops and
does not restart, problem is likely to be
leaking checkvalve on suction side of
pump system.
Water flow from open tap
i) Tank pre-charge set too high or too low i) Adjust tank pre-charge to 15kPa (2psi)
stops then starts when first ii) Pressure switch cut-in set too low
below cut-in
opened
ii) Adjust pressure switch cut-in
Tank will not hold air
i) Faulty air valve
i) Replace air valve core
pre-charge
ii) Punctured diaphragm
ii) Replace tank