Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual

9

Operation

Display Panel Functions

On Battery Operation

The UPS switches to battery operation automatically if the utility power fails. While running On Battery, an

alarm beeps four times every 30 seconds.
Press the

button to silence this alarm. If the utility power does not return, the UPS continues to supply

power to the connected equipment until the battery is fully discharged.
When 2 minutes of run time remain, the UPS emits a continuous beeping. If PowerChute is not being used,

files must be manually saved and the computer must be turned off before the UPS fully discharges the

battery.
Refer to www.apc.com for information on battery runtimes. The UPS battery runtime differs based on usage

and environment.

Utility Voltage Measurement

1. Press and hold the

button to view the utility voltage bar graph indicator.

2. After a few seconds, the five-LED Battery Charge

indicator will show the utility input voltage.

3. Refer to the appropriate voltage (100 or 110/120) reading. Values are not listed on the UPS. The actual

input voltage is between the displayed value on the list and the next higher value.

Feature

Button

Feature Title

Function

Power On

Press this button to turn on the UPS. Continue reading for additional

capabilities.

Power Off

Press this button to turn off the UPS output.

N

OTE

: The battery will continue to charge and the fans will continue to run

while the UPS is connected to the utility.

Cold Start

When there is no utility power and the UPS is off, press and hold the

button

to power up the UPS and connected equipment.
N

OTE

: The UPS will emit two beeps. During the second beep, release the button.

Self-Test

Automatic: The UPS performs a self-test automatically when tuned on, and

every two weeks thereafter (by default). During the self-test, the UPS briefly
operates the connected equipment On Battery.
Manual: Press and hold the

button

for a few seconds to initiate the self-test.

Feature Display

Feature Title

Description

Diagnostic Utility
Voltage

The UPS has a diagnostic feature that indicates the utility voltage
coming into the UPS. The UPS starts a self-test as part of this

procedure. The self-test does not affect the voltage display. See

“Troubleshooting,” beginning on page 15 for additional information.

118.0

100V

108.7
99.3
90.0
80.6

138.2

110/120V

128.8
119.5
110.1
100.8