Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual

11

Configuration Settings

High Bypass

Points

100V Models:

110V
120V Models:

133V

100V

• 107V
• 110V
• 113V
• 116V
• 119V
• 122V
• 125V
• 128V

110-120V
• 127V
• 130V
• 133V
• 136V
• 139V
• 142V
• 145V
• 148V

Maximum voltage that the UPS will pass to

connected equipment during internal bypass
operation.

Low Bypass

Points

100V Models:

78V
120V Models:

86V

100V

• 78V
• 80V
• 82V
• 84V
• 86V
• 88V
• 90V
• 92V

110-120V
• 86V
• 88V
• 90V
• 92V
• 94V
• 96V
• 98V
• 100V

Minimum voltage that the UPS will pass to

connected equipment during internal bypass
operation.

Output Frequency

Automatic
50

±

3 Hz or

60

±

3 Hz

Automatic
50

±

3 Hz or

50

±

0.1 Hz

60

±

3 Hz or

60

±

0.1 Hz

Sets the allowable UPS output frequency.

Whenever possible, the output frequency tracks
the input frequency.

Number of Battery

Packs

1

Number of connected

battery packs

Defines the number of connected battery packs

for proper run time prediction.
1 = internal battery module,

2 = one SURT192XLBP or SURT192XLBPJ, 3 =

two SURT192XLBP or SURT192XLBPJ, etc.

Function

Factory

Default

User Selectable

Choices

Description