American Power Conversion 990-2233A User Manual
Page 11
Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual
11
Configuration Settings
High Bypass
Points
100V Models:
110V
120V Models:
133V
100V
• 107V
• 110V
• 113V
• 116V
• 119V
• 122V
• 125V
• 128V
110-120V
• 127V
• 130V
• 133V
• 136V
• 139V
• 142V
• 145V
• 148V
Maximum voltage that the UPS will pass to
connected equipment during internal bypass
operation.
Low Bypass
Points
100V Models:
78V
120V Models:
86V
100V
• 78V
• 80V
• 82V
• 84V
• 86V
• 88V
• 90V
• 92V
110-120V
• 86V
• 88V
• 90V
• 92V
• 94V
• 96V
• 98V
• 100V
Minimum voltage that the UPS will pass to
connected equipment during internal bypass
operation.
Output Frequency
Automatic
50
±
3 Hz or
60
±
3 Hz
Automatic
50
±
3 Hz or
50
±
0.1 Hz
60
±
3 Hz or
60
±
0.1 Hz
Sets the allowable UPS output frequency.
Whenever possible, the output frequency tracks
the input frequency.
Number of Battery
Packs
1
Number of connected
battery packs
Defines the number of connected battery packs
for proper run time prediction.
1 = internal battery module,
2 = one SURT192XLBP or SURT192XLBPJ, 3 =
two SURT192XLBP or SURT192XLBPJ, etc.
Function
Factory
Default
User Selectable
Choices
Description