Troubleshooting guide, Table 8 – Sterling QVES User Manual
Page 25
25
Troubleshooting Guide
SYMPTOMS
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
Table 8
1. Reset manifold pressure. Refer to
"Operation".
2. Replace regulator section of combin-
ation gas valve or complete valve.
3. Check with local gas supplier for
proper orifi ce size and replace. Refer
to
"Operation".
1. Close air shutter. Refer to "Operation".
2. Check with local gas supplier for
proper orifi ce size and replace. Refer
to
"Operation".
1. Close air shutter.
2. Reduce pilot gas. Refer to "Operation".
3. Replace
orifi
ce.
4. Reset manifold pressure. Refer to
"Operation"; Replace regulator section
of combination gas valve or complete
valve; or Check with local gas supplier
for proper orifi ce size and replace.
Refer to "Operation".
1. Open air shutters. Refer to
"Operation".
2. Clean main burner ports.
3. Replace manifold assembly.
4. Clean draft hood.
5. Check for dust or lint at air mixer
opening and around the air shutter.
6. Clean combustion air inlet openings in
bottom panel, see "Installation".
1. Clean fl ue. Refer to "Installation".
2. Clean combustion air inlet openings in
bottom panel, see "Installation".
3. Clean heat exchanger.
4. Determine
cause and repair
accordingly.
1. Inspect all gas piping and repair.
2. Clean heat exchanger/fl ue.
3. Eliminate drafts. Refer to "Installation".
4. See
"Installation".
5. Clean draft hood.
1. Close air shutter. Refer to "Operation".
2. Clean main burner ports.
3. Reset manifold pressure. Refer to
"Operation".
4. Supply piping is inadequately sized.
Refer to "Installation".
5. Clean pilot orifi ce. Refer to
"Operation".
6. Eliminate drafts. Refer to "Installation".
7. Refer to "Installation".
1. Open all manual gas valves.
2. Replace fuse or turn on power supply.
3. Turn up thermostat
4. Check limit switch with continuity
tester. If open, replace limit switch.
5. Check wiring per diagrams.
1. Pressure regulator set too high.
2. Defective
Regulator.
3. Burner orifi ce too large.
1. Excessive primary air.
2. Burner orifi ce too small.
1. Too much primary air.
2. Noisy
pilot
3. Irregular orifi ce causing whistle or
resonance.
4. Excessive gas input.
1. Insuffi cient primary air.
2. Clogged main burner ports.
3. Misaligned
orifi
ces.
4. Clogged draft hood.
5. Air shutter linted.
6. Insuffi cient combustion air.
1. Blocked
venting.
2. Insuffi cient combustion air.
3. Blocked heat exchanger.
4. Air leak into combustion chamber or
draft
hood.
1. Shut off gas supply immediately!
2. Blocked heat exchanger/venting.
3. Drafts around heater.
4. Negative Pressure in building.
5. Blocked draft hood.
1. Excessive primary air.
2. Main burner ports clogged near pilot.
3. Pressure regulator set too low.
4. Pilot decreases in size when main
burners come on.
5. Pilot fl ame too small.
6. Drafts around heater.
7. Improper
venting.
1. Main gas off.
2. Lack of power at unit.
3. Thermostat not calling for heat.
4. Defective limit switch.
5. Improper thermostat or transformer
wiring at gas valve.
A. Flame lifting from burner
ports.
B. Flame pops back.
C. Noisy
fl
ame.
D. Yellow tip fl ame (some yellow
tipping on propane gas is
permissible).
E. Floating
fl
ame.
F. Gas
Odor.
G. Delayed ignition.
H. Failure to ignite.