10 vjxs-k ratio setter – Yokogawa JUXTA VJXS User Manual
Page 5

5
IM 77J01X11-01E
2nd Edition
Nov 30,2005-00
6.9
VJXS-J Linearizer (Optionally-set Line-segment
Function)
This computing unit gives an optional relationship between the input
(X) and output (output-1 = Y1, ouput-2 = Y2) signals using an option-
ally-set line-segment function. The line-segment function has 21
breakpoints, which each gives an input-output relationship as a per-
centage (%).
Set the number of line segments by 1 to 20.
Set the input (X) at % value in H01:CONST to H21:CONST, and the
output (Y) at % value in H22:CONST to H42:CONST.
●
Setting condition of breakpoints:
For input:
−
6.0
Ϲ
X
0
(H01) to X
20
(H21)
Ϲ
106.0%; with 4 significant
digits, minimum unit is 0.01%
X
0
1 2 < ····· 20 For output: − 6.0 Ϲ Y 0 (H22) to Y 20 (H42) Ϲ 106.0%; with 4 significant digits, minimum unit is 0.01% Ϲ X 0 (H01), Y 0 (H22) is output. When input м final set value, the final set value of output is output. Any number of line segments (1 to 20) can be set in H43. ● Computation accuracy: ± 0.1% (However, when line-segment gain is 1 or less.) 6.10 VJXS-K Ratio Setter This computing unit sets the ratio by the following expression. Output-1 signal (%) Y2: Output-2 signal (%) X: Input signal (%) K1: Ratio (no unit) A1, A2: Bias (%) Set the ratio (K1) in H01:CONST, and the bias (A1) at % value in ● Setting range of ratio: − 320 to 320 with 4 significant digits; minimum unit is 0.00001. ● Setting range of bias: − 32000 to 32000% with 4 significant digits; minimum unit is 0.001%. ● Computation accuracy: ± 0.1% (However, when the ratio is 1 or less.) NOTE Decide ratio or bias so as not to exceed ± 3.4 ϫ 10 38 % during computation. Ratio, bias and computation results are 4
When input
The number of line segments 1 to 20 corresponds 100 to 2000%.
Y1 = Y2 = K1 · (X+A1)+A2
where Y1:
H02:CONST, and the bias (A2) at % value in H03:CONST.
significant digits.