• Do not apply a voltage exceeding the value indicated below to the input
terminals of the 10-CH, High-Speed Digital Input module and the output
terminals of the 10-CH, Medium-Speed Digital Output module. Doing so can
damage the modules.
• Maximum input voltage
10-CH, High-Speed Digital Input Module: ± 10 VDC (-D05), ± 50 VDC (-D24)
10-CH, Medium-Speed Digital Output module: ± 250 VAC or 250 VDC
• Maximum common mode voltage
Input/output terminal to ground: 250 VACrms (50/60 Hz)
• Do not apply a voltage exceeding the value indicated below to the input
terminals of the analog output modules or the PWM output modules. Doing so
can damage the modules.
• Maximum common mode voltage
Output terminal to ground: 250 VACrms (50/60 Hz)
• The MX100 and MW100 are an overvoltage category II (IEC61010-1)
instrument. Measurement category II (IEC61010-2-30) is applied to the universal
input modules, the DCV/TC/DI input module, the Four-wire RTD resistance input
module, and the strain input module.
Wiring Procedure, Specifications, and Other Items Related to the Input/Output Modules
See the MX100/MW100 Data Acquisition Unit Installation and Connection Guide (IM
MX100-72E) provided with the main module, or the MX100 Data Acquisition Unit User’s
Manual (IM MX100-01E) or the MW100 Data Acquisition Unit User’s Manual (IM