beautypg.com

Client/server settings for write, Server-side settings, Client-side settings – Yokogawa Standalone MW100 User Manual

Page 5

background image

IM MW100-72E

Client/Server Settings for WRITE

Server-Side Settings

Server Settings

Set the MW100 server as the server device. These are the same as the server-side
settings for READ.

MATH Channel Settings

In order to display data written to the hold registers from the MW100 client, enter the
communication input channel numbers in the MATH channel expression entry area.
These are the same as the MATH channel settings for READ.

Client-Side Settings

Client Setting 1

Set the MW100 client as the client device. These are the same as the client-side settings
for READ.

Client Setting 2

Enter settings for the destination server. These are the same as the client-side settings
for READ.

Client Setting

Enter settings for registers to be used for sending data.

Select the register function (read

or write)

If the client will be writing to the server,

select Write.

• for Write

Enter the number of the

destination server

Enter the number set in Client Setting 2.

In the example, “1” is entered.

Enter the number of the first hold

register that is written to on the

destination server.

In the example, “40001” is entered since

the client will write to communication

input channels C001 to C004 on the

server.

Select the data type for the hold

registers of the destination

server.

In the example, “Float-Little” is entered

indicating that the register data type is

32-bit floating point.

Enter the channels on the client

that will be written to the

destination server

In the example, “A001” to “A004” is

entered since computed data from MATH

channels 001 to 004 are written.