Client Setting 2
Enter settings for the destination server.
Enter the IP address of the server
Enter the IP address or host name of the destination
server. In the example, an IP address of
“192.168.1.101” is entered.
Enter the server unit number
Only Modbus/TCP connections are used in the
example, therefore the default unit number of “255”
is used.
Enter the server port number
Enter the port number of the destination server.
In the example, “502” is entered.
Client Setting
Enter settings for registers to be used for receiving data. For data types, see “Register
Data Types."
Select the register function (read
or write)
If the client will be reading from the
server, select “Read.”
Enter the number of the destination
server
Enter the number set in Client Setting 2.
In the example, “1” is entered.
Enter the number of the first input
register on the destination server
that will be read.
In the example, “31001” is entered since the
measured data read out from measurement
channels 001 to 004 is of the 32-bit floating
point type.
Select the data type for the registers
on the destination server that will
be read.
In the example, “Float-Little” is entered
indicating that the register data type is
32-bit floating point and the order is lower
byte, upper byte.
Enter the communication input
channels on which to read by the
client
In the example, the client will read on
communication input channels “C001” to “C004.”
• for Read
MATH Channel Settings
In order to display data loaded to the communication input channels from the MW100
server, enter the communication input channel numbers in the MATH channel expression
entry area.