Client Setting 2

Enter settings for the destination server.

Enter the IP address of the server

Enter the IP address or host name of the destination

server. In the example, an IP address of

“192.168.1.101” is entered.

Enter the server unit number

Only Modbus/TCP connections are used in the

example, therefore the default unit number of “255”

is used.

Enter the server port number

Enter the port number of the destination server.

In the example, “502” is entered.

Client Setting

Enter settings for registers to be used for receiving data. For data types, see “Register
Data Types."

Select the register function (read

or write)

If the client will be reading from the

server, select “Read.”

Enter the number of the destination

server

Enter the number set in Client Setting 2.

In the example, “1” is entered.

Enter the number of the first input

register on the destination server

that will be read.

In the example, “31001” is entered since the

measured data read out from measurement

channels 001 to 004 is of the 32-bit floating

point type.

Select the data type for the registers

on the destination server that will

be read.

In the example, “Float-Little” is entered

indicating that the register data type is

32-bit floating point and the order is lower

byte, upper byte.

Enter the communication input

channels on which to read by the

client

In the example, the client will read on

communication input channels “C001” to “C004.”

• for Read

MATH Channel Settings

In order to display data loaded to the communication input channels from the MW100
server, enter the communication input channel numbers in the MATH channel expression
entry area.