The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
4
Electrical Specifications WFF165, IWF165, CWF165
165 liters / 35 pounds
Boiler Fed/Steam Heat
Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full
Load Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full
Load Amps
Recommended
Circuit Breaker (US-
market)
AWG/mm2
US NON-US
US NON-US
N
440-480 50/60
3
3+PE
4
10
10
14/2.5
6x3 kW
30
40
40
8/10.0
P
380-415 50/60
3
3+N+PE 12
15
16
14/2.5
38
50
50
8/10.0
Q
200-240 50/60
3
3+PE
12
15
16
14/2.5
57
70
70
4/25.0
X
200-240 50/60
1/3
2/3+PE
12
15
16
14/2.5
N/A N/A
N/A
N/A
Alternative Electric Heat Options
N
440-480 50/60
3
3+PE
3x3 kW +
3x2 kW
26
30
30
10/6.0
P
380-415 50/60
3
3+N+PE
34
40
40
8/10.0
Q
200-240 50/60
3
3+PE
50
60
60
6/16.0
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
N
440-480 50/60
3
3+PE
3x3 kW +
3x4 kW
34
40
40
8/10.0
P
380-415 50/60
3
3+N+PE
53
60
60
6/16.0
Q
200-240 50/60
3
3+PE
N/A N/A
N/A
N/A
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
N
440-480 50/60
3
3+PE
6x2 kW
21
30
30
10/6.0
P
380-415 50/60
3
3+N+PE
30
40
40
8/10.0
Q
200-240 50/60
3
3+PE
42
50
50
8/10.0
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
N
440-480 50/60
3
3+PE
6x4 kW
39
50
50
8/10.0
P
380-415 50/60
3
3+N+PE
47
60
60
6/16.0
Q
200-240 50/60
3
3+PE
N/A N/A
N/A
N/A
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
Table 6